3-Phase AC Circuits 2
3P AC Circuits 2
3-phase power measurement is the process of determining total active power in three-phase systems using one or more electrodynamometer wattmeters.
1. Power Measurement Using Wattmeter
Wattmeter is an electrodynamic instrument designed to measure active electric power in watts.
- Current coil has low resistance and connects in series with line
- Potential coil has high resistance and connects across load voltage
- Deflection angle is proportional to average active power
Wattmeter Power Reading
Where: \(W\) = wattmeter reading (W), \(V\) = potential coil voltage (V), \(I\) = current coil current (A), \(\theta\) = phase angle between \(V\) and \(I\) (\(^\circ\))
EE Board Exam October 1980
Example. Three equal impedances of \(8 + j7\ \Omega\) are connected in delta across a \(240\ \text{V}\), 3-phase line. Find the reading of a single-phase wattmeter with its current coil in line a and potential coil across lines b and c.
Solution.
Answer: \(6180\ \text{W}\)
2. 3-Phase Power Measurement with Balanced Load Using Single Wattmeter
Single-wattmeter method measures total 3-phase active power in balanced loads using one wattmeter and special potential connections.
2.1 Neutral Point Available
Neutral-point method connects the wattmeter potential coil directly between one line conductor and the system neutral.
- Measures single-phase active power
- Total 3-phase power equals three times reading
- Requires accessible 4-wire neutral conductor
Single Wattmeter with Neutral Available
Where: \(P_{\text{total}}\) = total active power (W), \(W\) = wattmeter reading (W)
2.2 Potential-Lead Shift Method
Potential-lead shift method connects current coil in line 1 and shifts potential lead sequentially to lines 2 and 3.
- First position gives reading \(W'\)
- Second position gives reading \(W''\)
- Total active power is sum of two readings
Potential-Lead Shift Method
Where: \(P_{\text{total}}\) = total active power (W), \(W'\) = first position reading (W), \(W''\) = second position reading (W)
Example. A wattmeter connected in line 1 of a \(230\ \text{V}\) 3-phase system reads \(5760\ \text{W}\) when connected to line 2 and \(3380\ \text{W}\) when shifted to line 3. Calculate the line current.
Solution.
Answer: \(25.168\ \text{A}\)
2.3 Artificial Neutral Method
Artificial neutral method creates a star point \(N\) using three equal non-inductive resistors \(R\) connected across lines.
- Star point potential equals true load neutral potential
- Potential coil connects between line 1 and artificial neutral \(N\)
- Total power equals three times wattmeter reading
Artificial Neutral Method
Where: \(P_{\text{total}}\) = total active power (W), \(W\) = wattmeter reading (W)
Example. An artificial neutral is formed using \(88.8\ \Omega\) resistors across a \(400\ \text{V}\) 3-phase line. If a wattmeter reads \(900\ \text{W}\), determine line current.
Solution.
Answer: \(2.6\ \text{A}\)
2.4 T-Method
T-method connects potential coil between line 1 and junction of two equal resistors \(R\) placed across lines 2 and 3.
- Creates midpoint potential reference between lines 2 and 3
- Wattmeter registers exactly half of total 3-phase power
- Total active power equals twice wattmeter reading
T-Method Power Formula
Where: \(P_{\text{total}}\) = total active power (W), \(W\) = wattmeter reading (W)
Example. In the T-method of measuring 3-phase power, a \(7.5\ \text{hp}\) motor operating at \(88\%\) efficiency is supplied by a 3-phase line. Calculate the wattmeter reading.
Solution.
Answer: \(3.179\ \text{kW}\)
2.5 CT Method
CT method utilizes two current transformers with secondaries paralleled in difference configuration through one wattmeter current coil.
- Current coil carries geometric difference of CT currents
- Single wattmeter reads total 3-phase power directly
- Suitable for high-voltage and high-current power measurement
CT Method Power Formula
Where: \(P_{\text{total}}\) = total active power (W), \(W\) = wattmeter reading (W)
3. n-Phase Power Measurement Using n Number of Wattmeters
n-wattmeter method measures active power in an \(n\)-phase \(n\)-wire system by placing one wattmeter current coil in each phase line.
- All potential coil leads join at common arbitrary junction \(O\)
- Valid for both balanced and unbalanced polyphase loads
- Total power equals algebraic sum of all \(n\) readings
n-Phase Power with n Wattmeters
Where: \(P_{\text{total}}\) = total active power (W), \(W_1, W_2, W_n\) = individual wattmeter readings (W)
EE Board Exam April 1993
Example. An unbalanced 3-phase load has Phase I at \(120\ \text{V}, 100\ \text{A}, 1.0\ pf\), Phase II at \(100\ \text{V}, 230\ \text{A}, 0.8\ pf\), and Phase III at \(110\ \text{V}, 85\ \text{A}, 0.77\ pf\). Calculate total power.
Solution.
Answer: \(37.6\ \text{kW}\)
4. n-Phase Power Measurement Using n-1 Number of Wattmeters
Blondel’s Theorem states that total power in any \(n\)-wire system is measured using \(n-1\) wattmeters by placing common reference point \(O\) on one conductor.
- Named after French engineer André Blondel
- Potential coil voltage on reference line becomes zero
- Eliminates one wattmeter without affecting total power accuracy
Blondel’s Theorem (n-1 Wattmeters)
Where: \(P_{\text{total}}\) = total active power (W), \(W_1, W_2\) = readings of remaining \((n-1)\) wattmeters (W)
Example. Two wattmeters connected using line c as common potential point measure an unbalanced load. If \(W_1 = 4140(60)\cos 30^\circ\ \text{W}\) and \(W_2 = 4140(78.4)\cos 26^\circ\ \text{W}\), find total power.
Solution.
Answer: \(506.85\ \text{kW}\)
5. Two-Wattmeter Reading When Load Is Balanced
Two-wattmeter method measures active power in 3-wire 3-phase circuits using two wattmeters connected across lines.
- \(W_1\) reads \(V_L I_L \cos(30^\circ - \theta)\)
- \(W_2\) reads \(V_L I_L \cos(30^\circ + \theta)\)
- Total active power \(P = W_1 + W_2\)
- Total reactive power \(Q = \sqrt{3}(W_1 - W_2)\)
Two-Wattmeter Readings (Balanced Load)
Where: \(W_1, W_2\) = wattmeter readings (W), \(V_L\) = line voltage (V), \(I_L\) = line current (A), \(\theta\) = load power factor angle (\(^\circ\)), \(P_{\text{total}}\) = total active power (W), \(Q_{\text{total}}\) = total reactive power (VAR)
EE Board Exam April 1984
Example. A balanced 3-phase load draws \(75\ \text{A}\) line current at \(230\ \text{V}\) line-to-line at \(0.848\) lagging power factor. Find two-wattmeter readings.
Solution.
Answer: \(17.24\ \text{kW}, 8.10\ \text{kW}\)
6. Power Factor Computation Using Two-Wattmeter
Power factor angle \(\theta\) is determined directly from the ratio or difference of two wattmeter readings \(W_1\) and \(W_2\).
- At \(pf = 1.0\), \(W_1 = W_2\)
- At \(pf = 0.5\), \(W_2 = 0\)
- At \(pf < 0.5\), \(W_2\) is negative (current coil reversed)
Power Factor Angle Formula
Where: \(\theta\) = power factor angle (\(^\circ\)), \(W_1, W_2\) = wattmeter readings (W), \(pf\) = load power factor
Example. Two wattmeters read \(4800\ \text{W}\) and \(400\ \text{W}\) after reversing its current coil on a 3-phase load. Solve for load power factor.
Solution.
Answer: \(0.439\)
7. Formula Summary
| Formula Name | Formula | Variables |
|---|---|---|
| Wattmeter Power Reading | \(W = V I \cos\theta\) | \(W\) = power (W), \(V\) = voltage (V), \(I\) = current (A), \(\theta\) = phase angle (\(^\circ\)) |
| Single Wattmeter with Neutral Available | \(P_{\text{total}} = 3 W\) | \(P_{\text{total}}\) = total active power (W), \(W\) = wattmeter reading (W) |
| Potential-Lead Shift Method | \(P_{\text{total}} = W' + W''\) | \(P_{\text{total}}\) = total active power (W), \(W', W''\) = readings (W) |
| Artificial Neutral Method | \(P_{\text{total}} = 3 W\) | \(P_{\text{total}}\) = total active power (W), \(W\) = wattmeter reading (W) |
| T-Method Power Formula | \(P_{\text{total}} = 2 W\) | \(P_{\text{total}}\) = total active power (W), \(W\) = wattmeter reading (W) |
| CT Method Power Formula | \(P_{\text{total}} = W\) | \(P_{\text{total}}\) = total active power (W), \(W\) = wattmeter reading (W) |
| n-Phase Power with n Wattmeters | \(P_{\text{total}} = W_1 + W_2 + \dots + W_n\) | \(P_{\text{total}}\) = total active power (W), \(W_1, W_2, W_n\) = readings (W) |
| Blondel’s Theorem (n-1 Wattmeters) | \(P_{\text{total}} = W_1 + W_2 + \dots + W_{n-1}\) | \(P_{\text{total}}\) = total active power (W), \(W_1, W_2\) = readings (W) |
| Two-Wattmeter Readings (Balanced Load) | \(W_1 = V_L I_L \cos(30^\circ - \theta)\) \(W_2 = V_L I_L \cos(30^\circ + \theta)\) \(P_{\text{total}} = W_1 + W_2\) \(Q_{\text{total}} = \sqrt{3}(W_1 - W_2)\) | \(W_1, W_2\) = wattmeter readings (W), \(V_L\) = line voltage (V), \(I_L\) = line current (A), \(\theta\) = power factor angle (\(^\circ\)), \(P_{\text{total}}\) = active power (W), \(Q_{\text{total}}\) = reactive power (VAR) |
| Power Factor Angle Formula | \(\tan\theta = \sqrt{3}\left(\dfrac{W_1 - W_2}{W_1 + W_2}\right)\) \(\theta = \tan^{-1}\left[\sqrt{3}\left(\dfrac{W_1 - W_2}{W_1 + W_2}\right)\right]\) \(pf = \cos\theta\) | \(\theta\) = power factor angle (\(^\circ\)), \(W_1, W_2\) = wattmeter readings (W), \(pf\) = power factor |