Transmission Lines
Transmission Lines
Transmission Line is a set of conductors used to transmit electrical power from generating stations to distribution substations or electrical loads.
1. Inductance of Single-Phase Two-Wire Lines
- Internal Flux Linkage: flux inside conductor contributing \(0.5 \times 10^{-7}\ \text{H/m}\)
- External Flux Linkage: flux lines outside conductor up to separation distance
- Adjusted Radius: fictitious radius \(r' = 0.7788 r\) accounting for internal flux
Single-Phase Two-Wire Inductance
Where: \(L\) = loop inductance per unit length (\(\text{H/m}\)), \(d\) = distance between conductor centers (\(\text{m}\)), \(r\) = physical radius of conductor (\(\text{m}\)), \(r'\) = fictitious adjusted conductor radius (\(\text{m}\))
2. Inductance of Composite Conductor Lines
- Stranded Conductors: composite conductors made of multiple parallel strands
- Mutual GMD: geometric mean of all distances between strands of different conductors
- Self GMD: geometric mean of distances between all strands within same conductor
Composite Conductor Line Inductance
Where: \(L_x, L_y\) = inductance of conductor groups x and y (\(\text{H/m}\)), \(L_{\text{total}}\) = total loop inductance (\(\text{H/m}\)), \(D_{mxy}\) = mutual GMD between conductors x and y (\(\text{m}\)), \(D_{sx}, D_{sy}\) = self GMD or GMR of conductors x and y (\(\text{m}\))
3. GMD of Various Conductor Set-Ups
- Solid Round Wire: self GMD equals \(0.7788 r\)
- Two Parallel Wires: mutual GMD equals center-to-center distance \(d\)
- Point Line in Circle: mutual GMD equals circle radius \(R\)
Self and Mutual Geometric Mean Distance
Where: \(D_s\) = self GMD or GMR (\(\text{m}\)), \(D_m\) = mutual GMD (\(\text{m}\)), \(r\) = wire radius (\(\text{m}\)), \(d_{ij}\) = distance between strand \(i\) of group x and strand \(j\) of group y (\(\text{m}\)), \(m, n\) = number of strands in groups x and y
Example. A single solid round copper wire has a diameter of \(0.50\ \text{inch}\). Determine its self GMD.
Solution.
Answer: \(0.1947\ \text{inch}\)
4. Average Inductance Per Phase of a 3-Phase Transmission Line
- Transposed Line: conductors rotated position regularly along line length
- Equivalent Spacing: geometric mean of three inter-phase distances
Three-Phase Line Average Inductance
Where: \(L\) = average inductance per phase (\(\text{H/m}\)), \(D_m\) = equivalent mutual GMD (\(\text{m}\)), \(D_s\) = equivalent self GMD (\(\text{m}\)), \(D_{AB}, D_{BC}, D_{CA}\) = mutual GMDs between phases (\(\text{m}\)), \(D_{AA}, D_{BB}, D_{CC}\) = self GMDs of individual phases (\(\text{m}\))
Example. Determine the mutual GMD of a three-phase single-circuit transmission line whose conductors are arranged in a triangular formation with distances between conductors of \(20\ \text{ft}\), \(20\ \text{ft}\), and \(38\ \text{ft}\).
Solution.
Answer: \(24.77\ \text{ft}\)
4.1 Single Circuit Transmission Line
- Three Conductors: one conductor per phase arranged horizontally or triangularly
- Equal Phase Self GMDs: \(D_{AA} = D_{BB} = D_{CC} = 0.7788 r\)
Single Circuit Self and Mutual GMD
Where: \(r\) = conductor radius (\(\text{m}\)), \(d_{ab}, d_{bc}, d_{ca}\) = inter-phase conductor center distances (\(\text{m}\))
EE Board March 1998
Example. A \(230\ \text{kV}\) transmission line is \(100\ \text{miles}\) long with horizontally arranged conductors with \(20\ \text{ft}\) spacing. \(R = 0.0969\ \Omega/\text{mile}\) and \(\text{GMR} = 0.0435\ \text{ft}\). Calculate total line reactance and impedance at \(60\ \text{Hz}\).
Solution.
Answer: \(9.69 + j77.19\ \text{ohms}\)
4.2 Double Circuit Transmission Line
- Parallel Circuits: two parallel conductors per phase on same tower
- Reduced Inductance: double circuit reduces per-phase inductance and impedance
Double Circuit GMD Equations
Where: \(D_{AB}\) = mutual GMD between phases A and B (\(\text{m}\)), \(D_{AA}\) = equivalent self GMD of phase A conductors (\(\text{m}\)), \(d_{ab}, d_{ab'}, d_{a'b}, d_{a'b'}\) = distances between parallel circuit conductors (\(\text{m}\)), \(d_{aa'}\) = distance between duplicate conductors of phase A (\(\text{m}\)), \(D_s = 0.7788 r\) = strand GMR (\(\text{m}\))
Example. A three-phase double-circuit line has a horizontal spacing of \(40\ \text{ft}\) and a vertical spacing between adjacent levels of \(25\ \text{ft}\). Determine the mutual GMD of the line.
Solution.
Answer: \(40.56\ \text{ft}\)
5. Line-to-Line Capacitance of Single-Phase Two-Wire Line
- Charge Accumulation: electric charge accumulates on conductor surfaces due to potential difference
- Free Space Permittivity: \(\varepsilon_0 = 8.854 \times 10^{-12}\ \text{F/m}\)
Line-to-Line Capacitance
Where: \(C\) = line-to-line capacitance per unit length (\(\text{F/m}\)), \(\varepsilon_0 = 8.854 \times 10^{-12}\ \text{F/m}\) = permittivity of free space, \(d\) = distance between conductor centers (\(\text{m}\)), \(r\) = radius of conductor (\(\text{m}\))
6. Capacitance to Ground of Single-Phase Two-Wire Line
- Neutral Ground Line: ground plane forms zero-potential reference line
- Double Capacitance: line-to-ground capacitance \(C_n\) equals twice line-to-line capacitance
Line-to-Ground Capacitance
Where: \(C_n\) = capacitance from line conductor to ground neutral (\(\text{F/m}\)), \(C\) = line-to-line capacitance (\(\text{F/m}\)), \(\varepsilon_0 = 8.854 \times 10^{-12}\ \text{F/m}\), \(d\) = separation distance (\(\text{m}\)), \(r\) = conductor radius (\(\text{m}\))
7. Capacitance to Ground of a Three-Phase Transmission Line
- Unadjusted Radius: physical radius \(r\) used for self GMD \(D_s'\) (no \(0.7788\) factor)
- Ground Image Method: image conductors below ground model earth potential surface
Three-Phase Line-to-Ground Capacitance
Where: \(C_n\) = line-to-ground capacitance per phase (\(\text{F/m}\)), \(D_m\) = mutual GMD (\(\text{m}\)), \(D_s' = r\) = self GMD for capacitance (\(\text{m}\)), \(H_m, H_s\) = mutual and self GMDs to fictitious image conductors below ground level (\(\text{m}\))
8. Short Transmission Line
- Line Length Limit: length \(\le 50\ \text{miles}\) (\(80\ \text{km}\)) and voltage \(< 20\ \text{kV}\)
- Negligible Capacitance: shunt capacitance charging current neglected entirely
- Series Impedance: total resistance \(R_L\) and inductive reactance \(X_L\) in series
Short Line Equivalent Circuit Equation
Where: \(\mathbf{E}_s, E_s\) = sending-end phase voltage vector and magnitude (V), \(\mathbf{E}_r, E_r\) = receiving-end phase voltage vector and magnitude (V), \(\mathbf{I}_r, I_r\) = receiving-end line current (A), \(R_L\) = total line resistance per phase (\(\Omega\)), \(X_L\) = total line inductive reactance per phase (\(\Omega\)), \(\theta_r\) = receiving-end power factor angle (deg), \(+\) for lagging pf, \(-\) for leading pf
EE Board April 1981
Example. A 3-phase, 3-wire, short transmission line has a resistance of \(3\ \Omega\) and a reactance of \(6\ \Omega\) per wire. At the receiving end, a balanced 3-phase load draws a line current of \(60\ \text{A}\), at \(13500\ \text{volts}\) line to line, \(0.90\) power factor lagging. Determine the voltage at the sending end.
Solution.
Answer: \(14143\ \text{V}\)
9. Medium Transmission Lines
- Line Length Range: length between \(51\ \text{miles}\) and \(150\ \text{miles}\) (\(80-240\ \text{km}\))
- Shunt Admittance Included: line charging current included as lumped shunt admittance \(Y = j\omega C\)
9.1 Nominal T
- Centralized Capacitance: total shunt admittance \(Y\) located at middle of line
- Split Series Impedance: line impedance split equally into two halves \(Z/2\)
Nominal-T Transmission Line Equations
Where: \(\mathbf{E}_s, \mathbf{E}_r\) = sending and receiving phase voltage vectors (V), \(\mathbf{I}_s, \mathbf{I}_r\) = sending and receiving line current vectors (A), \(Z = R_L + j X_L\) = total series impedance (\(\Omega\)), \(Y = j B_C\) = total shunt admittance (\(\text{S}\))
9.2 Nominal Pi
- Central Series Impedance: total series impedance \(Z\) located in middle branch
- Split Shunt Admittance: line shunt admittance divided equally into \(Y/2\) at both ends
Nominal-Pi Transmission Line Equations
Where: \(\mathbf{E}_s, \mathbf{E}_r\) = sending and receiving phase voltage vectors (V), \(\mathbf{I}_s, \mathbf{I}_r\) = sending and receiving line current vectors (A), \(Z = R_L + j X_L\) = total series impedance (\(\Omega\)), \(Y = j B_C\) = total line shunt admittance (\(\text{S}\))
EE Board October 1996
Example. A 3-phase, \(60\ \text{Hz}\) transmission line delivers \(20\ \text{MVA}\) to a load at \(66\ \text{kV}\) at \(80\%\) pf lagging. The total series impedance of each line is \(15 + j75\ \Omega\). If a nominal \(\pi\) circuit is used, what would be the transmission efficiency if the admittance is \(j0.0006\ \text{mhos}\)?
Solution.
Answer: \(90.81\%\)
10. Long Transmission Line
- Line Length Range: length exceeding \(150\ \text{miles}\) (\(240\ \text{km}\))
- Distributed Parameters: parameters \(R, L, C, G\) distributed uniformly per unit length
- Surge Impedance: characteristic impedance \(Z_0 = \sqrt{Z/Y}\)
Long Line Wave Equations
Where: \(\mathbf{E}_s, \mathbf{E}_r\) = sending and receiving phase voltage vectors (V), \(\mathbf{I}_r\) = receiving line current vector (A), \(Z_0\) = characteristic or surge impedance (\(\Omega\)), \(\gamma\) = propagation constant (\(\text{m}^{-1}\) or \(\text{mi}^{-1}\)), \(\ell\) = transmission line length (\(\text{m}\) or \(\text{miles}\))
11. Transmission Line Voltage Regulation
- Definition: percentage change in receiving-end voltage when full load is dropped
- Ferranti Effect: receiving voltage exceeds sending voltage at no load on long lines
Transmission Line Voltage Regulation
Where: \(\%\text{VR}\) = percent voltage regulation, \(E_s\) = no-load receiving-end voltage magnitude (equal to sending voltage \(E_s\)) (V), \(E_r\) = full-load receiving-end voltage magnitude (V)
12. Transmission Line Losses and Efficiency
- Line Conductor Loss: \(3 I_L^2 R_L\) total \(I^2R\) power loss in line conductors
- Transmission Efficiency: ratio of active power received at load to active power sent
Line Losses and Efficiency
Where: \(P_{\text{losses}}\) = total 3-phase line power loss (W), \(I_L\) = line current (A), \(R_L\) = resistance of one line conductor (\(\Omega\)), \(P_r\) = receiving-end active power (W), \(P_s\) = sending-end active power (W), \(\eta\) = transmission efficiency (%)
EE Board October 1980
Example. A short line has a resistance of \(4\ \Omega\) and a reactance of \(12\ \Omega\) per wire and transmits power to a concentrated load of \(1000\ \text{kVA}\), \(13200\ \text{volts}\), 3-phase, \(60\ \text{Hz}\), \(0.8\) pf inductive load. Find its efficiency.
Solution.
Answer: \(95.75\%\)
13. Formula Summary
| Formula Name | Formula | Variables |
|---|---|---|
| Single-Phase Two-Wire Inductance | \(L = 4 \times 10^{-7} \ln\left(\dfrac{d}{r'}\right)\) | \(L\) = inductance (\(\text{H/m}\)) \(d\) = spacing (\(\text{m}\)) \(r' = 0.7788 r\) (\(\text{m}\)) |
| Composite Conductor Inductance | \(L_x = 2 \times 10^{-7} \ln\left(\dfrac{D_{mxy}}{D_{sx}}\right)\) | \(L_x\) = phase inductance (\(\text{H/m}\)) \(D_{mxy}\) = mutual GMD (\(\text{m}\)) \(D_{sx}\) = self GMD (\(\text{m}\)) |
| Self GMD (GMR) | \(D_s = 0.7788 r\) | \(D_s\) = self GMD (\(\text{m}\)) \(r\) = conductor radius (\(\text{m}\)) |
| Three-Phase Average Inductance | \(L = 2 \times 10^{-7} \ln\left(\dfrac{D_m}{D_s}\right)\) | \(L\) = phase inductance (\(\text{H/m}\)) \(D_m\) = mutual GMD (\(\text{m}\)) \(D_s\) = self GMD (\(\text{m}\)) |
| Single Circuit Self GMD | \(D_{AA} = D_{BB} = D_{CC} = 0.7788 r\) | \(D_{AA}\) = self GMD (\(\text{m}\)) \(r\) = conductor radius (\(\text{m}\)) |
| Double Circuit Self GMD | \(D_{AA} = \sqrt{d_{aa'} D_s}\) | \(D_{AA}\) = phase self GMD (\(\text{m}\)) \(d_{aa'}\) = parallel distance (\(\text{m}\)) \(D_s\) = strand GMR (\(\text{m}\)) |
| Line-to-Line Capacitance | \(C = \dfrac{\pi \varepsilon_0}{\ln\left(\dfrac{d}{r}\right)}\) | \(C\) = capacitance (\(\text{F/m}\)) \(\varepsilon_0 = 8.854 \times 10^{-12}\ \text{F/m}\) \(d\) = spacing (\(\text{m}\)) \(r\) = radius (\(\text{m}\)) |
| Line-to-Ground Capacitance | \(C_n = \dfrac{2\pi \varepsilon_0}{\ln\left(\dfrac{d}{r}\right)}\) | \(C_n\) = ground capacitance (\(\text{F/m}\)) \(d\) = spacing (\(\text{m}\)) \(r\) = radius (\(\text{m}\)) |
| Three-Phase Line-to-Ground Capacitance | \(C_n = \dfrac{2\pi \varepsilon_0}{\ln\left(\dfrac{D_m}{D_s'}\right)}\) | \(C_n\) = ground capacitance (\(\text{F/m}\)) \(D_m\) = mutual GMD (\(\text{m}\)) \(D_s' = r\) (\(\text{m}\)) |
| Short Line Sending Voltage | \(\mathbf{E}_s = \mathbf{E}_r + \mathbf{I}_r (R_L + j X_L)\) | \(\mathbf{E}_s, \mathbf{E}_r\) = sending/receiving phase voltages (V) \(\mathbf{I}_r\) = current (A) \(R_L, X_L\) = resistance and reactance (\(\Omega\)) |
| Nominal-T Sending Voltage | \(\mathbf{E}_s = \mathbf{E}_r \left[1 + \dfrac{ZY}{2}\right] + \mathbf{I}_r Z \left[1 + \dfrac{ZY}{4}\right]\) | \(\mathbf{E}_s, \mathbf{E}_r\) = phase voltages (V) \(\mathbf{I}_r\) = current (A) \(Z\) = impedance (\(\Omega\)) \(Y\) = admittance (\(\text{S}\)) |
| Nominal-Pi Sending Voltage | \(\mathbf{E}_s = \mathbf{E}_r \left[1 + \dfrac{ZY}{2}\right] + \mathbf{I}_r Z\) | \(\mathbf{E}_s, \mathbf{E}_r\) = phase voltages (V) \(\mathbf{I}_r\) = current (A) \(Z\) = impedance (\(\Omega\)) \(Y\) = admittance (\(\text{S}\)) |
| Long Line Characteristic Impedance | \(Z_0 = \sqrt{\dfrac{Z}{Y}}\) | \(Z_0\) = surge impedance (\(\Omega\)) \(Z\) = total series impedance (\(\Omega\)) \(Y\) = total shunt admittance (\(\text{S}\)) |
| Voltage Regulation | \(\%\text{VR} = \dfrac{E_s - E_r}{E_r} \times 100\%\) | \(\%\text{VR}\) = percent regulation \(E_s\) = sending phase voltage (V) \(E_r\) = receiving phase voltage (V) |
| Line Power Loss | \(P_{\text{losses}} = 3 I_L^2 R_L\) | \(P_{\text{losses}}\) = 3-phase line loss (W) \(I_L\) = line current (A) \(R_L\) = line resistance (\(\Omega\)) |
| Transmission Efficiency | \(\eta = \dfrac{P_r}{P_s} \times 100\%\) | \(\eta\) = efficiency (\%) \(P_r\) = receiving power (W) \(P_s\) = sending power (W) |