Transformers 2
Transformers 2
3-Phase Transformer Bank is an arrangement of three single-phase transformers or one three-phase transformer unit used to step up or step down voltages in three-phase power systems.
1. Delta-Delta Transformer Bank
- Phase Voltage Equals Line Voltage: primary and secondary winding voltages match line voltages
- Closed Mesh Connection: secondary continues operating if one phase is disconnected
- Zero Phase Shift: line voltages on primary and secondary remain in phase
Delta-Delta Voltage and Current Relations
Where: \(V_1, V_2\) = primary and secondary line voltages (V), \(V_p, V_s\) = primary and secondary phase voltages (V), \(I_1, I_2\) = primary and secondary line currents (A), \(I_p, I_s\) = primary and secondary phase currents (A), \(a\) = turns ratio
Example. A \(150\ \text{kVA}\), \(3\phi\) load is connected to a delta-delta transformer bank with turns ratio \(N_1/N_2 = 1/2\). If the secondary line voltage is \(4160\ \text{V}\), calculate the primary phase current.
Solution.
Answer: \(6.01\ \text{A}\)
2. Delta-Wye Transformer Bank
- Step-Up Application: commonly used at generating stations to elevate distribution voltage
- Secondary Neutral Available: neutral wire provides 3-phase 4-wire service
- Phase Angle Displacement: secondary line voltage leads primary line voltage by \(30^\circ\)
Delta-Wye Voltage and Current Relations
Where: \(V_1, V_2\) = primary and secondary line voltages (V), \(V_p, V_s\) = primary and secondary phase voltages (V), \(I_1, I_2\) = primary and secondary line currents (A), \(I_p, I_s\) = primary and secondary phase currents (A), \(a = N_1/N_2\) = turns ratio per phase
Example. A delta-wye transformer bank has a turns ratio of \(96\) to \(1\). If the secondary line voltage is \(4160\ \text{V}\), find the primary line voltage.
Solution.
Answer: \(230\ \text{kV}\)
3. Wye-Delta Transformer Bank
- Step-Down Application: used at distribution substations to reduce high transmission voltage
- Stable Secondary Voltage: delta secondary suppresses third-harmonic voltages
- Phase Angle Displacement: secondary line voltage lags primary line voltage by \(30^\circ\)
Wye-Delta Voltage and Current Relations
Where: \(V_1, V_2\) = primary and secondary line voltages (V), \(V_p, V_s\) = primary and secondary phase voltages (V), \(I_1, I_2\) = primary and secondary line currents (A), \(I_p, I_s\) = primary and secondary phase currents (A), \(a = N_1/N_2\) = turns ratio per phase
EE Board Exam October 1997
Example. A power transformer rated \(50000\ \text{kVA}\), \(34.5\ \text{kV}/13.8\ \text{kV}\) is connected wye-grounded primary and delta on the secondary. Determine the full load phase current on the secondary side.
Solution.
Answer: \(1208\ \text{A}\)
4. Wye-Wye Transformer Bank
- Economical Insulation: winding insulation rated for phase voltage (\(V_L/\sqrt{3}\))
- Neutral Grounding Required: neutral must be grounded to prevent third-harmonic distortion
- Zero Phase Shift: line voltages on primary and secondary remain in phase
Wye-Wye Voltage and Current Relations
Where: \(V_1, V_2\) = primary and secondary line voltages (V), \(V_p, V_s\) = primary and secondary phase voltages (V), \(I_1, I_2\) = primary and secondary line currents (A), \(a = N_1/N_2\) = turns ratio per phase
EE Board Exam October 1997
Example. A power transformer rated \(50000\ \text{kVA}\), \(34.5\ \text{kV}/13.8\ \text{kV}\) is connected wye-wye. What are the line currents at full load?
Solution.
Answer: \(836.7\ \text{A}\ \text{and}\ 2092\ \text{A}\)
5. Open Delta Transformer Bank
- V-V Connection: uses two single-phase transformers to supply a three-phase load
- Reduced Bank Capacity: delivers \(57.7\%\) of closed delta bank capacity
- Individual Transformer Loading: each transformer operates at \(86.6\%\) of its kVA rating
Open Delta Capacity Formulas
Where: \(S_v\) = total kVA capacity of open delta bank (kVA), \(S_\Delta\) = total kVA capacity of closed delta bank (kVA), \(S_{\text{unit}}\) = kVA rating of one single-phase transformer (kVA)
EE Board Exam June 1990
Example. What should be the kVA rating of each two transformers in an open-delta bank when the three-phase balanced load is \(290.4\ \text{kVA}\)?
Solution.
Answer: \(167.66\ \text{kVA}\)
6. Scott or T-Connected Transformer Bank
- Phase Transformation: converts 3-phase power to 2-phase power or vice versa
- Main Transformer: single-phase unit with \(50\%\) center tap on primary winding
- Teaser Transformer: single-phase unit with \(86.6\%\) (\(\sqrt{3}/2\)) tap on primary winding
Scott Connection Voltage and Turns Relations
Where: \(V_L\) = primary 3-phase line voltage (V), \(V_2\) = secondary 2-phase line voltage (V), \(N_{1(\text{main})}, N_{1(\text{teaser})}\) = primary turns of main and teaser transformers, \(N_2\) = secondary turns
Example. A Scott-connected transformer bank converts \(416\ \text{V}\) 3-phase to \(6600\ \text{V}\) 2-phase. If the secondary has \(1500\ \text{turns}\), find the primary turns for the main and teaser transformers.
Solution.
Answer: \(95\ \text{turns (main)}\ \text{and}\ 82\ \text{turns (teaser)}\)
7. Parallel Operation
- Voltage Rating Identity: primary and secondary voltage ratings must be identical
- Polarity Requirement: transformers must be connected with correct relative polarity
- Equal Impedance Ratio: ratio of equivalent resistance to reactance (\(R_e/X_e\)) should match
7.1 Unequal Turns Ratio
- No-Load Circulating Current: flows between windings due to induced voltage difference
- Load Division Inequality: transformer with higher secondary emf carries larger load
Parallel Operation with Unequal Turns Ratio
Where: \(a_1, a_2\) = voltage ratios of transformers 1 and 2, \(V_2\) = terminal load voltage (V), \(Z_{e1}, Z_{e2}\) = equivalent secondary impedances (\(\Omega\)), \(I_t\) = total load current (A), \(I_1, I_2\) = load currents delivered by transformers 1 and 2 (A)
7.2 Equal Turns Ratio (Ohmic Equi Impedance)
- Zero Circulating Current: no current flows between transformers at no load
- Impedance Inverse Division: shared load current varies inversely as internal impedance
Parallel Load Sharing (Ohmic Impedances)
Where: \(I_t\) = total load current (A), \(S_t\) = total load apparent power (kVA), \(S_1, S_2\) = apparent power delivered by transformers 1 and 2 (kVA), \(Z_{e1}, Z_{e2}\) = equivalent secondary impedances (\(\Omega\))
EE Board Exam October 1985
Example. Two transformers are connected in parallel to supply a common load of \(175\ \text{kVA}\). Transformer A is rated \(100\ \text{kVA}\) with equivalent impedance of \(9.6\ \Omega\) while Transformer B is rated \(75\ \text{kVA}\) with equivalent impedance of \(12.5\ \Omega\). Find the kVA load of each transformer.
Solution.
Answer: \(99\ \text{kVA}\ \text{and}\ 76\ \text{kVA}\)
7.3 Equal Turns Ratio (Per Unit Impedance Different Power Base)
- Common Base Conversion: convert all per-unit impedances to a chosen base kVA
- Proportional Loading: transformers share load in proportion to kVA ratings if per-unit impedances are equal
Parallel Load Sharing (Per-Unit Impedances)
Where: \(Z_{\text{pu,old}}, Z_{\text{pu,new}}\) = original and converted per-unit impedances, \(Z_{e1}', Z_{e2}'\) = per-unit impedances on common base, \(S_t\) = total load (kVA), \(S_1, S_2\) = kVA carried by transformers 1 and 2
EE Board Exam March 1998
Example. A \(125\text{-kVA}\) distribution transformer with \(4\%\) impedance is connected in parallel with another transformer rated \(75\text{-kVA}\) and with \(3\%\) impedance. Both have the same voltage ratio. Neglecting resistance, how much load does each carry when supplying \(140\ \text{kVA}\) total?
Solution.
Answer: \(77.78\ \text{kVA}\ \text{and}\ 62.22\ \text{kVA}\)
8. Formula Summary
| Formula Name | Formula | Variables |
|---|---|---|
| Delta-Delta Voltage Ratio | \(\dfrac{V_1}{V_2} = \dfrac{V_p}{V_s} = a\) | \(V_1, V_2\) = line voltages (V) \(V_p, V_s\) = phase voltages (V) \(a\) = turns ratio |
| Delta-Delta Current Ratio | \(\dfrac{I_1}{I_2} = \dfrac{\sqrt{3} I_p}{\sqrt{3} I_s} = \dfrac{1}{a}\) | \(I_1, I_2\) = line currents (A) \(I_p, I_s\) = phase currents (A) \(a\) = turns ratio |
| Delta-Wye Voltage Ratio | \(\dfrac{V_1}{V_2} = \dfrac{V_p}{\sqrt{3} V_s} = \dfrac{a}{\sqrt{3}}\) | \(V_1, V_2\) = line voltages (V) \(V_p, V_s\) = phase voltages (V) \(a\) = turns ratio |
| Delta-Wye Current Ratio | \(\dfrac{I_1}{I_2} = \dfrac{\sqrt{3} I_p}{I_s} = \dfrac{\sqrt{3}}{a}\) | \(I_1, I_2\) = line currents (A) \(I_p, I_s\) = phase currents (A) \(a\) = turns ratio |
| Wye-Delta Voltage Ratio | \(\dfrac{V_1}{V_2} = \dfrac{\sqrt{3} V_p}{V_s} = \sqrt{3} a\) | \(V_1, V_2\) = line voltages (V) \(V_p, V_s\) = phase voltages (V) \(a\) = turns ratio |
| Wye-Delta Current Ratio | \(\dfrac{I_1}{I_2} = \dfrac{I_p}{\sqrt{3} I_s} = \dfrac{1}{\sqrt{3} a}\) | \(I_1, I_2\) = line currents (A) \(I_p, I_s\) = phase currents (A) \(a\) = turns ratio |
| Wye-Wye Voltage Ratio | \(\dfrac{V_1}{V_2} = \dfrac{\sqrt{3} V_p}{\sqrt{3} V_s} = a\) | \(V_1, V_2\) = line voltages (V) \(V_p, V_s\) = phase voltages (V) \(a\) = turns ratio |
| Open Delta Capacity | \(S_v = \sqrt{3} S_{\text{unit}}\) | \(S_v\) = open delta capacity (kVA) \(S_{\text{unit}}\) = single transformer rating (kVA) |
| Open Delta Capacity Ratio | \(\dfrac{S_v}{S_\Delta} = \dfrac{\sqrt{3}}{3} = 0.577\) | \(S_v\) = open delta capacity (kVA) \(S_\Delta\) = closed delta capacity (kVA) |
| Scott Teaser Voltage | \(V_{\text{teaser(pri)}} = 0.866 V_L\) | \(V_{\text{teaser(pri)}}\) = teaser primary voltage (V) \(V_L\) = 3-phase line voltage (V) |
| Scott Primary Turns | \(\dfrac{N_{1(\text{teaser})}}{N_2} = 0.866 a\) | \(N_{1(\text{teaser})}\) = teaser primary turns \(N_2\) = secondary turns \(a\) = line turns ratio |
| Parallel Load Current (Unequal Ratio) | \(I_1 = \dfrac{(a_2 - a_1)V_2 + (a_2 Z_{e2} I_t)}{a_1 Z_{e1} + a_2 Z_{e2}}\) | \(I_1\) = load current of transformer 1 (A) \(a_1, a_2\) = voltage ratios \(Z_{e1}, Z_{e2}\) = impedances (\(\Omega\)) |
| Parallel Load Current (Equal Ratio) | \(I_1 = \dfrac{I_t Z_{e2}}{Z_{e1} + Z_{e2}}\) | \(I_1\) = current of transformer 1 (A) \(I_t\) = total load current (A) \(Z_{e1}, Z_{e2}\) = impedances (\(\Omega\)) |
| Parallel Load Sharing (kVA) | \(S_1 = \dfrac{S_t Z_{e2}}{Z_{e1} + Z_{e2}}\) | \(S_1\) = load on transformer 1 (kVA) \(S_t\) = total load (kVA) \(Z_{e1}, Z_{e2}\) = impedances (\(\Omega\)) |
| Per-Unit Base Change | \(Z_{\text{pu,new}} = Z_{\text{pu,old}} \left(\dfrac{\text{kVA}_{\text{base,new}}}{\text{kVA}_{\text{base,old}}}\right)\) | \(Z_{\text{pu,new}}\) = per-unit impedance on new base \(Z_{\text{pu,old}}\) = per-unit impedance on old base |
| Parallel Load Sharing (Per-Unit) | \(S_1 = \dfrac{S_t Z_{e2}'}{Z_{e1}' + Z_{e2}'}\) | \(S_1\) = load on transformer 1 (kVA) \(S_t\) = total load (kVA) \(Z_{e1}', Z_{e2}'\) = per-unit impedances on common base |