Transformers 1
Transformers 1
Transformer is a static electrical machine that transfers electrical energy between two or more circuits through electromagnetic induction without a change in frequency.
1. Induced EMF Equation
- Primary Induced EMF: voltage induced in primary winding turns
- Secondary Induced EMF: voltage induced in secondary winding turns
- EMF Per Turn: induced voltage divided by number of turns
Induced EMF Equation
Where: \(E\) = rms induced voltage (V), \(N\) = number of winding turns, \(f\) = frequency (Hz), \(\Phi_m\) = peak magnetic flux (Wb), \(e_t\) = induced emf per turn (V/turn), \(\beta_m\) = peak flux density (T), \(A\) = core cross-sectional area (\(\text{m}^2\))
Example. Calculate the total magnetic flux in a \(60\ \text{Hz}\) transformer in which the induced emf per turn of the winding is equal to \(2\ \text{V}\).
Solution.
Answer: \(7.5\ \text{mWb}\)
2. Equivalent Circuit of an Ideal Transformer
- Lossless Core: zero hysteresis and zero eddy current losses
- Zero Winding Resistance: no copper loss in primary or secondary
- Zero Leakage Flux: total flux links both windings completely
Ideal Transformer Ratios
Where: \(a\) = turns ratio or transformation ratio, \(N_1, N_2\) = primary and secondary turns, \(E_1, E_2\) = primary and secondary induced voltages (V), \(I_1, I_2\) = primary and secondary currents (A), \(Z_1, Z_2\) = primary and secondary impedances (\(\Omega\))
Example. The low side of a welding transformer has \(2\ \text{turns}\) and delivers \(300\ \text{A}\). If the high voltage side has \(30\ \text{turns}\), how much current flows through it?
Solution.
Answer: \(20\ \text{A}\)
3. Equivalent Circuit of a Practical Transformer
- Primary Winding Resistance: resistance of primary coil conductors (\(R_1\))
- Primary Leakage Reactance: reactance due to primary leakage flux (\(X_1\))
- Secondary Winding Resistance: resistance of secondary coil conductors (\(R_2\))
- Secondary Leakage Reactance: reactance due to secondary leakage flux (\(X_2\))
- Exciting Branch: parallel combination of \(R_m\) and \(X_m\)
Practical Transformer Core Parameters
Where: \(S_m\) = core apparent power (VA), \(Q_m\) = magnetizing reactive power (var), \(P_m\) = iron or core loss (W), \(R_m\) = resistance representing iron losses (\(\Omega\)), \(X_m\) = magnetizing reactance (\(\Omega\)), \(E_1\) = primary induced voltage (V), \(I_0\) = exciting current (A)
4. Equivalent Circuit of Practical Transformer at No-Load
- Open Secondary: secondary current \(I_2 = 0\) at no load
- Exciting Current: small primary current \(I_0\) flowing into shunt branch
- Core Loss Component: in-phase current component supplying iron loss (\(I_c\))
- Magnetizing Component: quadrature current component establishing flux (\(I_m\))
No-Load Exciting Current Relations
Where: \(I_0\) = no-load exciting current (A), \(I_c\) = core loss current component (A), \(I_m\) = magnetizing current component (A), \(\theta_0\) = no-load power factor angle (deg)
5. Equivalent Circuit of Practical Transformer at Full-Load
- Secondary Load Current: load draws current \(I_2\) at terminal voltage \(V_2\)
- Primary Load Component: additional primary current \(I_1' = I_2/a\) balancing load
- Total Primary Current: vector sum of exciting current \(I_0\) and \(I_1'\)
Full-Load Current and Voltage Relations
Where: \(\mathbf{I}_1\) = total primary line current (A), \(\mathbf{I}_1'\) = load component of primary current (A), \(\mathbf{I}_0\) = exciting current (A), \(\mathbf{V}_g\) = primary terminal supply voltage (V), \(\mathbf{V}_2\) = secondary terminal load voltage (V), \(R_1, R_2\) = primary and secondary resistances (\(\Omega\)), \(X_1, X_2\) = primary and secondary reactances (\(\Omega\))
6. Shifting Transformer Parameters from Primary to Secondary and Vice Versa
- Referred to Secondary: primary impedance divided by turns ratio squared (\(a^2\))
- Referred to Primary: secondary impedance multiplied by turns ratio squared (\(a^2\))
- Equivalent Resistance: total circuit resistance combined on one side
- Equivalent Reactance: total leakage reactance combined on one side
Parameter Shifting Relations
Where: \(R_{e1}, R_{e2}\) = total equivalent resistance referred to primary and secondary (\(\Omega\)), \(X_{e1}, X_{e2}\) = total equivalent reactance referred to primary and secondary (\(\Omega\)), \(a = \dfrac{N_1}{N_2} = \dfrac{V_1}{V_2}\) = turns ratio
7. Equivalent Circuit of a Transformer Referred to the Secondary Side
- Simplified Model: exciting branch neglected and all series impedance moved to secondary
- Secondary Series Drop: voltage drop caused by \(I_2 R_{e2}\) and \(I_2 X_{e2}\)
- Power Angle: angle \(\delta\) between secondary induced voltage \(E_2\) and terminal voltage \(V_2\)
Secondary Referred Circuit Voltage Equation
Where: \(E_2\) = secondary induced voltage or no-load secondary voltage (V), \(V_2\) = secondary terminal load voltage (V), \(I_2\) = secondary load current (A), \(R_{e2}\) = equivalent resistance referred to secondary (\(\Omega\)), \(X_{e2}\) = equivalent reactance referred to secondary (\(\Omega\)), \(\theta\) = load power factor angle (deg), \(+\) for lagging pf, \(-\) for leading pf
EE Board October 1991
Example. A \(10\ \text{kVA}\), \(2400/240\ \text{V}\) single-phase transformer has \(r_1 = 3\ \Omega, x_1 = 15\ \Omega, r_2 = 0.03\ \Omega, x_2 = 0.15\ \Omega\). Find the primary voltage required to produce \(240\ \text{V}\) at the secondary terminals at full load, \(0.80\) power factor lagging.
Solution.
Answer: \(2496.5\ \text{V}\)
8. Open-Circuit Test of Transformers
- Low Voltage Side: instruments connected to low voltage winding
- High Voltage Side Open: high voltage winding left open-circuited
- Rated Voltage Applied: rated low-side voltage applied during test
- Core Loss Measurement: wattmeter reading represents constant core/iron losses
Open-Circuit Test Equations
Where: \(P_{oc}\) = wattmeter reading during open-circuit test (W), \(P_{\text{core}}\) = total core or iron loss (W), \(V_{oc}\) = applied rated open-circuit voltage (V), \(I_{oc}\) = no-load exciting current (A), \(\cos\theta_0\) = no-load power factor
9. Short-Circuit Test on Transformers
- High Voltage Side: instruments connected to high voltage winding
- Low Voltage Side Shorted: low voltage winding short-circuited with thick conductor
- Reduced Voltage Applied: small voltage applied until rated current flows
- Copper Loss Measurement: wattmeter reading represents full-load copper loss
Short-Circuit Test Parameters
Where: \(P_{sc}\) = wattmeter reading during short-circuit test (W), \(P_{\text{cuFL}}\) = full-load copper loss (W), \(E_{sc}\) = applied short-circuit voltage (V), \(I_{sc}\) = rated short-circuit current (A), \(Z_e\) = equivalent impedance (\(\Omega\)), \(R_e\) = equivalent resistance (\(\Omega\)), \(X_e\) = equivalent reactance (\(\Omega\))
EE Board April 1993
Example. A short circuit test was performed upon a \(10\ \text{kVA}\), \(2300/230\ \text{V}\) transformer with results: \(E_{sc} = 137\ \text{V}\), \(P_{sc} = 192\ \text{W}\), \(I_{sc} = 4.34\ \text{A}\). Calculate in primary terms the reactance of the transformer.
Solution.
Answer: \(29.88\ \text{ohms}\)
10. Power Losses and Efficiency
- Core Loss: sum of eddy current and hysteresis losses (\(P_{\text{core}}\))
- Copper Loss: \(I^2 R\) loss in primary and secondary windings (\(P_{\text{cu}}\))
- Efficiency: ratio of output power to input power
Power Losses and Efficiency Equations
Where: \(\eta\) = efficiency (\%), \(P_{\text{out}}\) = output power (W), \(P_{\text{in}}\) = input power (W), \(P_{\text{core}}\) = core or iron loss (W), \(P_{\text{cu}}\) = winding copper loss (W), \(V_2\) = load terminal voltage (V), \(I_2\) = load current (A), \(\cos\theta\) = load power factor
EE Board April 1990
Example. A \(50\ \text{kVA}\), \(2300/230\ \text{V}\), \(60\ \text{Hz}\) transformer gives \(187\ \text{W}\) on open-circuit test and \(570\ \text{W}\) on short-circuit test. Determine the efficiency of the transformer at half load, unity power factor.
Solution.
Answer: \(98.70\%\)
11. Copper Losses at Any Size of Load
- Variable Loss: copper loss varies as square of current or load fraction
- Fractional Load: ratio of operating kVA or current to rated value (\(x\))
Copper Loss at Fractional Load
Where: \(P_{\text{cu}_x}\) = copper loss at fractional load \(x\) (W), \(P_{\text{cu}_{\text{FL}}}\) = full-load copper loss (W), \(x\) = fractional load or percentage loading
Example. The iron loss of a \(25\ \text{kVA}\), \(60\ \text{Hz}\) single-phase distribution transformer is \(1\%\) of the rated output at unity power factor and full-load copper loss is \(360\ \text{W}\). Determine the efficiency when operating one half of the rated output at \(70\%\) power factor lagging.
Solution.
Answer: \(96.26\%\)
12. Maximum Efficiency
- Maximum Condition: variable copper loss equals constant core loss
- Load at Peak Efficiency: fractional load \(x_m = \sqrt{P_{\text{core}}/P_{\text{cu}_{\text{FL}}}}\)
Maximum Efficiency Equations
Where: \(x_m\) = fractional load for maximum efficiency, \(\text{kVA}_m\) = load kVA for maximum efficiency, \(P_{\text{core}}\) = core loss (W), \(P_{\text{cu}_{\text{FL}}}\) = full-load copper loss (W), \(\eta_{\max}\) = maximum efficiency (\%), \(P_{\text{out}_m}\) = output power at maximum efficiency load (W)
Example. A \(10\ \text{kVA}\), \(2300/230\ \text{V}\) transformer has an equivalent resistance referred to the secondary winding of \(0.05\ \Omega\). The core loss is \(75\ \text{W}\). At what kVA load will this transformer operate at maximum efficiency?
Solution.
Answer: \(8.90\ \text{kVA}\)
13. All-Day Efficiency
- Energy Efficiency: ratio of 24-hour energy output to 24-hour energy input
- Distribution Transformer: operates 24 hours continuously with varying load
- Constant Core Loss Energy: core loss energy equals \(P_{\text{core}} \times 24\ \text{hours}\)
All-Day Efficiency Equations
Where: \(\eta_{\text{all-day}}\) = all-day energy efficiency (\%), \(W_{\text{out}}\) = total output energy in 24 hours (\(\text{kWh}\)), \(W_{\text{core}}\) = total core loss energy in 24 hours (\(\text{kWh}\)), \(W_{\text{cu}}\) = total copper loss energy in 24 hours (\(\text{kWh}\)), \(t\) = time duration of load (hours)
EE Board October 1980 / EE Board October 1982
Example. A \(25\ \text{kVA}\) distribution transformer operates at \(20\%\) overload, \(0.30\) pf lagging for \(1\ \text{hr}\); full load, \(0.90\) lagging pf for \(3\ \text{hrs}\); \(50\%\) load at unity pf for \(8\ \text{hrs}\); and \(10\%\) load at \(0.80\) leading pf for the rest of the day (\(12\ \text{hrs}\)). If core loss is \(150\ \text{W}\) and full-load copper loss is \(500\ \text{W}\), what is the all-day efficiency?
Solution.
Answer: \(96.68\%\)
14. Per-Unit Values
- Percent Resistance: ratio of full-load resistive drop to rated voltage
- Percent Reactance: ratio of full-load reactive drop to rated voltage
- Percent Impedance: ratio of short-circuit voltage to rated voltage
Percent and Per-Unit Parameter Equations
Where: \(\%\text{IR}\) = percent resistance, \(\%\text{IX}\) = percent reactance, \(\%\text{IZ}\) = percent impedance, \(P_{sc}\) = short-circuit test copper loss (W), \(E_{sc}\) = short-circuit test voltage (V), \(\text{VA}_{\text{rating}}\) = rated apparent power (VA), \(V_{\text{rated}}\) = rated voltage (V)
EE Board April 1983
Example. A single-phase transformer rated \(75\ \text{kVA}\), \(8000\ \text{V}\) primary \(240\ \text{V}\) secondary, is given the short circuit test. With the secondary terminals short-circuited, \(440\ \text{V}\) (\(60\ \text{Hz}\)) is impressed on the primary, which then draws rated current and \(1125\ \text{W}\). Solve for the percentage impedance of the transformer.
Solution.
Answer: \(5.50\%\)
15. Voltage Regulation
- Definition: percentage change in secondary terminal voltage from full load to no load
- Lagging Load: voltage drops under load, causing positive regulation
- Leading Load: voltage rise possible under load, causing negative regulation
Voltage Regulation Equations
Where: \(\%\text{VR}\) = percent voltage regulation, \(E_2\) = secondary no-load voltage (V), \(V_2\) = secondary full-load voltage (V), \(\%\text{IR}\) = percent resistance, \(\%\text{IX}\) = percent reactance, \(\theta\) = load power factor angle (deg), \(+\) for lagging pf, \(-\) for leading pf
EE Board April 1990
Example. Short circuit test on a \(100\ \text{kVA}\), \(2400/240\ \text{V}\) distribution transformer gave: \(E_{sc} = 72\ \text{V}\), \(I_{sc} = 41.6\ \text{A}\), \(P_{sc} = 1180\ \text{W}\). Calculate the percent regulation at a power factor of \(0.75\) lagging.
Solution.
Answer: \(2.71\%\)
16. Autotransformer
- Single Winding: one continuous winding common to both primary and secondary
- Common Winding Current: difference between primary and secondary currents (\(I_c\))
- Transformed Power: power transferred via magnetic induction
- Conducted Power: power transferred directly via electrical conduction
Autotransformer Equations
Where: \(a\) = turns or voltage ratio (\(V_1/V_2 > 1\) for step-down), \(V_1, V_2\) = primary and secondary voltages (V), \(I_1, I_2\) = primary and secondary currents (A), \(I_c\) = common winding current (A), \(P_{\text{input}}\) = total input VA or power (W)
Example. A \(20000\ \text{VA}\), \(400/500\ \text{V}\) autotransformer operates at full load. Determine the current flowing in the common winding.
Solution.
Answer: \(10\ \text{A}\)
17. Current Transformer
- Series Instrument Transformer: primary connected in series with high current line
- Ammeter Secondary: secondary connected to standard 5-ampere AC ammeter
- Line Current Formula: line current equals ammeter reading times CT ratio
Current Transformer Equation
Where: \(I_L\) = actual line current to be measured (A), \(A\) = ammeter reading (A), \(\text{CT ratio}\) = nominal current transformation ratio of current transformer
Example. An ammeter connected to a \(100/5\) current transformer reads \(4\ \text{A}\). Calculate the actual line current.
Solution.
Answer: \(80\ \text{A}\)
18. Potential Transformer
- Parallel Instrument Transformer: primary connected across high voltage line
- Voltmeter Secondary: secondary connected to standard 115-volt AC voltmeter
- Line Voltage Formula: line voltage equals voltmeter reading times PT ratio
Potential Transformer Equation
Where: \(V_L\) = actual high voltage line potential (V), \(V\) = voltmeter reading (V), \(\text{PT ratio}\) = nominal voltage transformation ratio of potential transformer
EE Board October 1998
Example. The potential transformer of a line has a ratio of \(132000/66\). The voltmeter reads \(64\ \text{V}\). What is the voltage of the line?
Solution.
Answer: \(128\ \text{kV}\)
15. Formula Summary
| Formula Name | Formula | Variables |
|---|---|---|
| Induced EMF Equation | \(E = 4.44 N f \Phi_m\) | \(E\) = induced rms voltage (V) \(N\) = number of turns \(f\) = frequency (Hz) \(\Phi_m\) = peak flux (Wb) |
| Induced EMF per Turn | \(e_t = 4.44 f \Phi_m\) | \(e_t\) = induced emf per turn (V/turn) \(f\) = frequency (Hz) \(\Phi_m\) = peak flux (Wb) |
| Peak Magnetic Flux | \(\Phi_m = \beta_m A\) | \(\Phi_m\) = peak flux (Wb) \(\beta_m\) = flux density (T) \(A\) = core area (\(\text{m}^2\)) |
| Ideal Transformer Voltage Ratio | \(a = \dfrac{N_1}{N_2} = \dfrac{E_1}{E_2} = \dfrac{V_1}{V_2}\) | \(a\) = turns ratio \(N_1, N_2\) = primary and secondary turns \(V_1, V_2\) = primary and secondary voltages (V) |
| Ideal Transformer Current Ratio | \(\dfrac{I_1}{I_2} = \dfrac{N_2}{N_1} = \dfrac{1}{a}\) | \(I_1, I_2\) = primary and secondary currents (A) \(a\) = turns ratio |
| Ideal Transformer Impedance Ratio | \(\dfrac{Z_1}{Z_2} = \left(\dfrac{N_1}{N_2}\right)^2 = a^2\) | \(Z_1, Z_2\) = primary and secondary impedances (\(\Omega\)) \(a\) = turns ratio |
| Core Loss Resistance | \(R_m = \dfrac{E_1^2}{P_m}\) | \(R_m\) = core loss resistance (\(\Omega\)) \(E_1\) = primary induced voltage (V) \(P_m\) = core loss (W) |
| Magnetizing Reactance | \(X_m = \dfrac{E_1^2}{Q_m}\) | \(X_m\) = magnetizing reactance (\(\Omega\)) \(E_1\) = primary induced voltage (V) \(Q_m\) = reactive magnetizing power (var) |
| No-Load Exciting Current | \(I_0 = \sqrt{I_c^2 + I_m^2}\) | \(I_0\) = exciting current (A) \(I_c\) = core loss current component (A) \(I_m\) = magnetizing current component (A) |
| Exciting Current Components | \(I_c = I_0 \cos\theta_0\) \(I_m = I_0 \sin\theta_0\) |
\(I_c\) = core loss current (A) \(I_m\) = magnetizing current (A) \(\theta_0\) = no-load power factor angle (deg) |
| Total Primary Current | \(\mathbf{I}_1 = \mathbf{I}_0 + \mathbf{I}_1' = \mathbf{I}_0 + \dfrac{\mathbf{I}_2}{a}\) | \(\mathbf{I}_1\) = total primary current (A) \(\mathbf{I}_0\) = exciting current (A) \(\mathbf{I}_2\) = secondary current (A) \(a\) = turns ratio |
| Equivalent Primary Resistance | \(R_{e1} = R_1 + a^2 R_2\) | \(R_{e1}\) = total resistance referred to primary (\(\Omega\)) \(R_1, R_2\) = primary and secondary resistances (\(\Omega\)) \(a\) = turns ratio |
| Equivalent Primary Reactance | \(X_{e1} = X_1 + a^2 X_2\) | \(X_{e1}\) = total reactance referred to primary (\(\Omega\)) \(X_1, X_2\) = primary and secondary reactances (\(\Omega\)) \(a\) = turns ratio |
| Equivalent Secondary Resistance | \(R_{e2} = R_2 + \dfrac{R_1}{a^2}\) | \(R_{e2}\) = total resistance referred to secondary (\(\Omega\)) \(R_1, R_2\) = primary and secondary resistances (\(\Omega\)) \(a\) = turns ratio |
| Equivalent Secondary Reactance | \(X_{e2} = X_2 + \dfrac{X_1}{a^2}\) | \(X_{e2}\) = total reactance referred to secondary (\(\Omega\)) \(X_1, X_2\) = primary and secondary reactances (\(\Omega\)) \(a\) = turns ratio |
| Secondary Induced Voltage | \(E_2 = \sqrt{(V_2 \cos\theta + I_2 R_{e2})^2 + (V_2 \sin\theta \pm I_2 X_{e2})^2}\) | \(E_2\) = secondary no-load voltage (V) \(V_2\) = secondary load voltage (V) \(I_2\) = secondary current (A) \(R_{e2}\) = equivalent resistance (\(\Omega\)) \(X_{e2}\) = equivalent reactance (\(\Omega\)) |
| Open-Circuit Power Factor | \(\cos\theta_0 = \dfrac{P_{oc}}{V_{oc} I_{oc}}\) | \(\cos\theta_0\) = no-load power factor \(P_{oc}\) = open-circuit test power (W) \(V_{oc}\) = open-circuit voltage (V) \(I_{oc}\) = no-load current (A) |
| Equivalent Short-Circuit Impedance | \(Z_e = \dfrac{E_{sc}}{I_{sc}}\) | \(Z_e\) = equivalent impedance (\(\Omega\)) \(E_{sc}\) = short-circuit test voltage (V) \(I_{sc}\) = rated short-circuit current (A) |
| Equivalent Short-Circuit Resistance | \(R_e = \dfrac{P_{sc}}{I_{sc}^2}\) | \(R_e\) = equivalent resistance (\(\Omega\)) \(P_{sc}\) = short-circuit test power (W) \(I_{sc}\) = short-circuit current (A) |
| Equivalent Short-Circuit Reactance | \(X_e = \sqrt{Z_e^2 - R_e^2}\) | \(X_e\) = equivalent reactance (\(\Omega\)) \(Z_e\) = equivalent impedance (\(\Omega\)) \(R_e\) = equivalent resistance (\(\Omega\)) |
| Transformer Efficiency | \(\eta = \dfrac{P_{\text{out}}}{P_{\text{out}} + P_{\text{core}} + P_{\text{cu}}} \times 100\%\) | \(\eta\) = efficiency (\%) \(P_{\text{out}}\) = output power (W) \(P_{\text{core}}\) = core loss (W) \(P_{\text{cu}}\) = copper loss (W) |
| Copper Loss at Fractional Load | \(P_{\text{cu}_x} = x^2 P_{\text{cu}_{\text{FL}}}\) | \(P_{\text{cu}_x}\) = copper loss at fractional load \(x\) (W) \(x\) = load fraction \(P_{\text{cu}_{\text{FL}}}\) = full-load copper loss (W) |
| Fractional Load for Max Efficiency | \(x_m = \sqrt{\dfrac{P_{\text{core}}}{P_{\text{cu}_{\text{FL}}}}}\) | \(x_m\) = load fraction at maximum efficiency \(P_{\text{core}}\) = core loss (W) \(P_{\text{cu}_{\text{FL}}}\) = full-load copper loss (W) |
| Maximum Efficiency Load kVA | \(\text{kVA}_m = \text{Rated kVA} \times \sqrt{\dfrac{P_{\text{core}}}{P_{\text{cu}_{\text{FL}}}}}\) | \(\text{kVA}_m\) = load kVA at max efficiency \(P_{\text{core}}\) = core loss (W) \(P_{\text{cu}_{\text{FL}}}\) = full-load copper loss (W) |
| All-Day Efficiency | \(\eta_{\text{all-day}} = \dfrac{W_{\text{out}}}{W_{\text{out}} + W_{\text{core}} + W_{\text{cu}}} \times 100\%\) | \(\eta_{\text{all-day}}\) = all-day efficiency (\%) \(W_{\text{out}}\) = total output energy (\(\text{kWh}\)) \(W_{\text{core}}\) = core loss energy (\(\text{kWh}\)) \(W_{\text{cu}}\) = copper loss energy (\(\text{kWh}\)) |
| Percent Resistance | \(\%\text{IR} = \dfrac{I_2 R_{e2}}{V_2} \times 100\% = \dfrac{P_{sc}}{\text{VA}_{\text{rating}}} \times 100\%\) | \(\%\text{IR}\) = percent resistance \(I_2 R_{e2}\) = resistive drop (V) \(P_{sc}\) = short-circuit power (W) |
| Percent Impedance | \(\%\text{IZ} = \dfrac{E_{sc}}{V_{\text{rated}}} \times 100\% = \dfrac{I_2 Z_{e2}}{V_2} \times 100\%\) | \(\%\text{IZ}\) = percent impedance \(E_{sc}\) = short-circuit voltage (V) \(V_{\text{rated}}\) = rated voltage (V) |
| Percent Reactance | \(\%\text{IX} = \sqrt{(\%\text{IZ})^2 - (\%\text{IR})^2}\) | \(\%\text{IX}\) = percent reactance \(\%\text{IZ}\) = percent impedance \(\%\text{IR}\) = percent resistance |
| Percent Voltage Regulation | \(\%\text{VR} = \dfrac{E_2 - V_2}{V_2} \times 100\%\) | \(\%\text{VR}\) = percent voltage regulation \(E_2\) = no-load voltage (V) \(V_2\) = full-load voltage (V) |
| Voltage Regulation from Percent Drops | \(\%\text{VR} = \sqrt{(\cos\theta + \%\text{IR})^2 + (\sin\theta \pm \%\text{IX})^2} - 1\) | \(\%\text{VR}\) = percent voltage regulation \(\theta\) = power factor angle (deg) \(\%\text{IR}\) = percent resistance \(\%\text{IX}\) = percent reactance |
| Autotransformer Common Winding Current | \(I_c = |I_1 - I_2|\) | \(I_c\) = common winding current (A) \(I_1, I_2\) = primary and secondary currents (A) |
| Autotransformer Transformed Power | \(P_{\text{transformed}} = P_{\text{input}} \left(1 - \dfrac{1}{a}\right)\) | \(P_{\text{transformed}}\) = power transferred by induction (W) \(P_{\text{input}}\) = total input power (W) \(a\) = voltage ratio (\(V_1/V_2 > 1\)) |
| Current Transformer Line Current | \(I_L = A \times \text{CT ratio}\) | \(I_L\) = line current (A) \(A\) = ammeter reading (A) \(\text{CT ratio}\) = primary to secondary current ratio |
| Potential Transformer Line Voltage | \(V_L = V \times \text{PT ratio}\) | \(V_L\) = line voltage (V) \(V\) = voltmeter reading (V) \(\text{PT ratio}\) = primary to secondary voltage ratio |