Cable Ampacity Calculator (IEC 60287): Underground, Duct Bank and Free-Air Ratings with Minimum Conductor Size

Table of Contents

Engineering Disclaimer: This content is for educational/informational purposes only. Always verify calculations and designs with a licensed engineer before applying them to actual construction or projects.
01

Cable Ampacity Calculator

Pick an example from Load example to see a complete case, then change one value at a time. Press the ? beside any input for its meaning, typical values and where to find it on the data sheet. Switch the mode to Find minimum size when you have a required current instead of a cable. Print / PDF report gives you the inputs, drawings and every calculation step.

Cable Ampacity Calculator IEC 60287 · single-core

Rate a single-core power cable, or find the minimum conductor size for a required current, using the IEC 60287 method. Press ? beside any input for its meaning, typical values and where to find it on the cable data sheet.

A

The construction below (insulation, screen, sheath, installation and layout) is kept, and every IEC 60228 conductor size is tried. The conductor you enter is the reference for diameter scaling.

1 · Conductor & voltage

mm²
mm
Ω/km
kV

2 · Cable construction

°C
Layer (inside → out)Thickness mmρT K·m/W
② Conductor binder tape
③ Conductor screen
④ Insulation
⑤ Insulation screen
⑥ Bedding / swelling tape

⑦ Metallic screen

mm
mm²
mm

⑧ Tapes over screen & ⑨ outer sheath

mm
mm
K·m/W
mm
K·m/W
Drawn to scale from your inputs. Click into a field to highlight its layer.

3 · Installation

°C
K·m/W
mm
mm
K·m/W
K·m/W
K·m/W
mm
mm
mm
mm
W/m²

4 · Layout & bonding

mm
mm
mm
mm
Installation cross-section

5 · Short-circuit & load checks (optional)

s
kA
°C
°C
kA
°C
°C
A
Calculating…

Steady-state rating to IEC 60287-1-1 and IEC 60287-2-1 at 100 % load factor, equally loaded circuits. Not covered: cyclic or emergency ratings (IEC 60853), three-core or armoured cables, external heat sources and soil drying-out. For engineering checks and education — confirm final ratings with project-specific soil data.

Reminder: This content is for educational/informational purposes only. Always verify calculations and designs with a licensed engineer before applying them to actual construction or projects. The calculator gives steady-state ratings at 100 % load factor for single-core, unarmoured cables with equally loaded circuits. Cyclic and emergency ratings (IEC 60853), three-core and armoured cables, external heat sources and soil drying-out are not covered.
02

Reading the Cable Data Sheet into the Calculator

The form follows a typical data sheet from the conductor outwards, then moves to the installation. The cross-section drawing updates as you type, so you can check each diameter against the data sheet line by line.

Which conductor data do I need?

  • Material and construction: copper or aluminium; round compacted or Milliken (segmental). The construction sets the skin and proximity coefficients ks and kp from IEC 60287-1-1 Table 2.
  • Area and diameter: nominal mm² and the “diameter of conductor” line. Quick-fill buttons give typical compacted diameters for every IEC 60228 size.
  • Max. DC resistance at 20 °C: always on the data sheet. Leave it blank to use the IEC 60228 maximum; the results flag a data-sheet value above that maximum.
  • U₀ and frequency: used for the dielectric loss, which only matters from about 60 kV up. A 50 Hz data sheet is slightly optimistic for a 60 Hz system.

How do the insulation and screen layers map to the drawing?

Layers are numbered ① conductor to ⑨ outer sheath, and the same numbers appear on the inputs, the drawing and the build-up table. Everything between the conductor and the metallic screen — conductor screen, insulation, insulation screen and any water-swelling tape — forms the insulation thermal resistance T1. Everything between the screen and the surface forms T3.

Data sheets rarely list every tape. Swelling tapes and the laminated aluminium foil over the screen are often missing. Enter the data-sheet overall diameter and tick Fit tapes to TDS OD: the calculator back-calculates that layer so the drawn cable matches the data sheet exactly.

What installation and layout data are needed?

  • Ground temperature at cable depth in the hottest month — not the air temperature — and the soil thermal resistivity for the driest season.
  • Ducts: type, outside and inside diameter, wall resistivity, and whether the duct is dry, flooded or filled with bentonite.
  • Duct bank: leave Auto-fit bank to ducts on and give the concrete cover, or untick it to enter an existing bank. Ducts outside the bank are drawn in red and the calculation stops.
  • Layout: trefoil or flat, touching or spaced, depth to the top row, and up to 6 × 6 equally loaded circuits.
  • Screen bonding: both-ends, single-point or cross-bonded. For large cables this one setting can halve the rating — see the worked example.
03

The IEC 60287 Method Behind the Numbers

IEC 60287 treats the cable and its surroundings as a thermal circuit: losses generated in the conductor, insulation and screen flow outwards through thermal resistances in series, and the rating is the current that brings the conductor to its maximum temperature.

What is the rating equation?

Steady-state rating, single-core unarmoured cable (IEC 60287-1-1 §1.4.1)
\( I = \left[\dfrac{\Delta\theta – W_d\left(\tfrac{1}{2}T_1 + T_3 + T_4\right)}{R\,T_1 + R\,(1+\lambda_1)(T_3 + T_4)}\right]^{1/2} \)

Variables

  • Δθ: conductor temperature rise above ambient (K)
  • R: AC resistance at maximum temperature (Ω/m); Wd: dielectric loss (W/m)
  • λ1: screen loss as a fraction of conductor loss
  • T1, T3, T4: insulation, outer sheath and external thermal resistances (K·m/W)

For a group of cables, the calculator replaces T4 with the cable’s own external resistance plus the mutual-heating terms from every other cable, each weighted by that cable’s own losses. It evaluates every cable and the hottest one sets the rating.

How are the conductor, dielectric and screen losses found?

AC resistance with skin and proximity effect (IEC 60287-1-1 §2.1)
\( R = R'(1 + y_s + y_p) \qquad R’ = R_0\left[1 + \alpha_{20}(\theta – 20)\right] \qquad x_s^2 = \dfrac{8\pi f}{R’}\,10^{-7}\,k_s \qquad y_s = \dfrac{x_s^4}{192 + 0.8\,x_s^4} \)
Dielectric loss (IEC 60287-1-1 §2.2)
\( W_d = \omega\,C\,U_0^2 \tan\delta \qquad C = \dfrac{\varepsilon}{18\ln\left(D_i/d_c\right)}\,10^{-9} \)
Circulating-current loss, screens bonded at both ends, trefoil (IEC 60287-1-1 §2.3.1); flat formation uses the outer/centre-cable variants
\( \lambda_1′ = \dfrac{R_s}{R}\,\dfrac{1}{1 + \left(\dfrac{R_s}{X}\right)^2} \qquad X = 2\omega\,10^{-7}\ln\dfrac{2s}{d} \)

Single-point and cross-bonded screens carry no circulating current, so λ1′ = 0; eddy-current loss λ1″ is then calculated for tubular sheaths. IEC practice neglects eddy loss in wire screens; a toggle lets you include it as a check.

How are the thermal resistances calculated?

Insulation and outer sheath — summed layer by layer (IEC 60287-2-1 §2.1)
\( T_1 = \sum \dfrac{\rho_T}{2\pi}\ln\dfrac{D_{out}}{D_{in}} \qquad T_3 = \sum \dfrac{\rho_T}{2\pi}\ln\dfrac{D_{out}}{D_{in}} \)
Buried cable with mutual heating by the image method (IEC 60287-2-1 §2.2.3)
\( T_4 = \dfrac{\rho_{soil}}{2\pi}\left[\ln\left(u + \sqrt{u^2 – 1}\right) + \sum_k \ln\dfrac{d’_{pk}}{d_{pk}}\right] \qquad u = \dfrac{2L}{D_e} \)

Variables

  • L: depth to cable centre; De: cable (or duct) outside diameter
  • d_pk: distance to cable k; d'_pk: distance to the image of cable k above ground
Cable in a duct: air gap, duct wall, then the surroundings (IEC 60287-2-1 §2.2.7)
\( T_4′ = \dfrac{U}{1 + 0.1\,(V + Y\theta_m)\,D_e} \qquad T_4” = \dfrac{\rho_d}{2\pi}\ln\dfrac{D_o}{D_d} \)
Duct bank correction for concrete ρc in native soil ρe, bank equivalent radius rb
\( \Delta T_4”’ = \dfrac{N}{2\pi}(\rho_e – \rho_c)\ln\left(u + \sqrt{u^2 – 1}\right) \qquad u = \dfrac{L_G}{r_b} \)
Cable in free air, iterated on the surface temperature rise (IEC 60287-2-1 §2.2.1)
\( T_4^* = \dfrac{1}{\pi D_e\, h\,(\Delta\theta_s)^{1/4}} \qquad h = \dfrac{Z}{D_e^{\,g}} + E \)
04

Worked Example: 72.5 kV 1200 mm² Cable in a Duct Bank

This is the first entry in Load example. Load it and you’ll get the same numbers.

Example inputs
Cable38/66 (72.5) kV, 1 × 1200 mm² Cu Milliken, XLPE 11.5 mm, 77 × 1.5 mm Cu wire screen, PE sheath, De = 88 mm
InstallationConcrete duct bank 720 × 480 mm, centre 1.0 m deep; PVC ducts 160/147 mm
Layout2 circuits stacked, flat, 240 mm spacing; top row at 0.91 m, second at 1.15 m
ThermalSoil 1.2 K·m/W, concrete 1.0 K·m/W, ground 30 °C, conductor 90 °C
BondingCross-bonded, 50 Hz

What does the calculator return?

Results — governing cable: circuit 2 (lower row), centre phase
QuantityValue
AC resistance at 90 °C, R0.02011 Ω/km (ys = 0.0406, yp = 0.0036)
Dielectric loss, Wd0.154 W/m
Screen loss factor, λ10 (cross-bonded, wire screen)
T1 / T30.3077 / 0.1130 K·m/W
T4 own (air gap 0.2948 + duct wall 0.0809 + external 0.5344 + bank correction 0.0591)0.9692 K·m/W
Mutual heating from the other five cables1.9351 K·m/W
Continuous rating943 A
Conductor temperatures at 943 AUpper row 85.0 / 88.1 / 85.0 °C; lower row 86.9 / 90.0 / 86.9 °C
Mutual heating is twice the cable’s own T4. The five neighbours contribute 1.94 K·m/W against 0.97 K·m/W for the cable on its own. That’s why the lower centre cable, surrounded on three sides, governs.

What happens if the screens are bonded at both ends instead?

With 136 mm² of copper screen and 240 mm spacing, the circulating current is large: the solidly-bonded λ1′ is 2.34, meaning the screens would generate more than twice the conductor loss.

Same duct bank, bonding changed
Cross-bonded or single-point: 943 A · Both-ends bonded: 480 A
= the rating drops by about half
For large single-core cables, bonding is a design decision, not a detail. If a data sheet quotes a rating without stating the bonding, ask — the difference here is almost 2 : 1.

What if I need 900 A — what’s the smallest conductor?

Switch to Find minimum size and enter 900 A. The calculator keeps the insulation, screen, sheath, duct bank and layout, scales the conductor diameter from the one entered, and tries every IEC 60228 size.

Sizing results — same construction and duct bank
SizeConductor ØOverall ØRating
800 mm²34.5 mm80.3 mm750 A
1000 mm²38.5 mm84.3 mm874 A — too small
1200 mm²42.2 mm88.0 mm943 A — minimum size
1400 mm²45.6 mm91.4 mm1,018 A

Below 1000 mm² the calculator treats Milliken conductors as compact round, because segmental conductors aren’t made that small. The real outer sheath usually grows a little on larger sizes, so confirm the final diameter with the supplier.

05

What Moves the Rating Most?

The base case is a typical distribution cable — 8.7/15 kV, 1 × 240 mm² Cu XLPE with a 25 mm² wire screen, buried in trefoil at 1.0 m, 60 Hz, screens bonded both ends — rated at 453 A with 1.2 K·m/W soil and 30 °C ground. Each row changes one input from that base case.

How sensitive is the rating to soil, temperature and depth?

15 kV 240 mm² Cu, direct buried trefoil — base case 453 A
ChangeRatingvs base
Soil ρ 0.7 K·m/W (very moist)565 A+25 %
Soil ρ 1.0 K·m/W489 A+8 %
Soil ρ 1.5 K·m/W412 A−9 %
Soil ρ 2.0 K·m/W362 A−20 %
Soil ρ 2.5 K·m/W (dry sand)327 A−28 %
Ground 25 °C / 35 °C472 A / 434 A±4 %
Depth 0.8 m / 1.5 m464 A / 436 A+2 % / −4 %
Second circuit alongside, 600 mm apart404 A−11 %
Single-point bonded instead of both ends464 A+2 %
In free air, 35 °C, shaded / in full sun598 A / 457 A—
Soil resistivity dominates. Going from moist to dry soil cuts the rating by more than 40 %, while depth and bonding (on a cable this size) move it by only a few percent. Spend your effort on a thermal survey and a stable backfill before fine-tuning the cable.
06

Why Your Result May Differ from the Supplier’s Data Sheet

A data-sheet rating is only valid for the conditions it was calculated under, which are often printed in small type or not at all. When your number and the supplier’s disagree, check these first.

Which assumptions usually explain the difference?

  • Soil resistivity and ground temperature: 1.0 K·m/W at 20 °C gives a much higher rating than 1.2 K·m/W at 30 °C.
  • Bonding: single-point or cross-bonded versus both-ends bonded — the largest effect on big cables.
  • Load factor: ratings calculated with a daily load factor below 100 % are higher than the steady-state IEC 60287 value.
  • Frequency: a 50 Hz rating is slightly optimistic on a 60 Hz system.
  • Grouping and spacing: a single isolated circuit versus your actual number of circuits.
  • Coefficients: Milliken ks, eddy loss in wire screens, and layer resistivities differ between software and IEC editions — usually only a few percent.
Validation. For the duct-bank example above, a CYMCAP 7.2 study of the same cable and layout gives 943.2 A with the same pattern of conductor temperatures. A hand calculation of a 132 kV lead-sheathed cable in a trench, done to IEC 60287, is also reproduced value by value up to the rating equation.
07

Frequently Asked Questions

Is IEC 60287 the same as Neher–McGrath?

They share the same physics: IEC 60287 grew out of the 1957 Neher–McGrath paper. Both use a thermal circuit, the image method for soil and mutual heating, and the same duct air-gap formula in different units. The main difference is load factor: Neher–McGrath builds daily load cycling into the earth term, while IEC 60287 rates at 100 % load and handles cycling separately in IEC 60853. The NEC’s engineering-supervision calculation uses Neher–McGrath, with RHO 90 (0.9 K·m/W) and 20 °C as the table basis.

What happens when the cable or duct is flooded?

The rating goes up, because water conducts heat far better than air. Choose Water (flooded duct) under duct filling: the duct example above goes from 943 A dry to 967 A flooded. The calculator treats the water as still and the cable as centred, which is conservative. Only use it for ducts that are permanently under water; a duct that dries out in summer must be rated dry.

Water-swelling tapes don’t change the rating. They stop water from travelling along the cable if the sheath is damaged, protecting the insulation from water treeing. Thermally they are modelled as thin dry tape layers.

Can soil around a loaded cable dry out?

Yes. Heat from the cable drives moisture away, and dried soil can reach 2–3 K·m/W, which can lead to thermal runaway. IEC 60287-2-1 covers this with a two-zone soil model that this calculator doesn’t include, so use the soil resistivity for the driest season, or a thermally stable backfill around the cables.

Does the calculator check short-circuit ratings too?

Yes, adiabatically per IEC 60949: I = K·S·√[ln((θf + β)/(θi + β))/t]. For the 1200 mm² copper conductor, 90 → 250 °C in 1 s gives 171.7 kA. The screen check takes a non-adiabatic factor ε if you want to reproduce a supplier’s figure.

08

Summary of Equations

Rating equation (single-core, unarmoured)
\( I = \left[\dfrac{\Delta\theta – W_d\left(\tfrac{1}{2}T_1 + T_3 + T_4\right)}{R\,T_1 + R\,(1+\lambda_1)(T_3 + T_4)}\right]^{1/2} \)
Losses
\( R = R'(1 + y_s + y_p) \qquad W_d = \omega C U_0^2 \tan\delta \qquad \lambda_1′ = \dfrac{R_s}{R}\,\dfrac{1}{1 + (R_s/X)^2} \)
Thermal resistances
\( T = \dfrac{\rho_T}{2\pi}\ln\dfrac{D_{out}}{D_{in}} \qquad T_4 = \dfrac{\rho}{2\pi}\left[\ln\left(u + \sqrt{u^2-1}\right) + \sum_k \ln\dfrac{d’_{pk}}{d_{pk}}\right] \qquad T_4′ = \dfrac{U}{1 + 0.1(V + Y\theta_m)D_e} \)
Short circuit (adiabatic)
\( I_{sc} = K\,S\,\sqrt{\dfrac{\ln\left(\dfrac{\theta_f + \beta}{\theta_i + \beta}\right)}{t}} \)
Summary: A cable’s continuous rating is set by how easily its losses can escape to the surroundings. For buried cables that is mostly the soil — its thermal resistivity, temperature and the heat from neighbouring circuits — while for large single-core cables the screen bonding can matter just as much. Rate the cable with the installation it will really have, and use the sizing mode to find the smallest conductor that carries the current you need.

References: IEC 60287-1-1, Electric cables — Calculation of the current rating — Part 1-1: Current rating equations (100 % load factor) and calculation of losses. IEC 60287-2-1, Part 2-1: Thermal resistance — Calculation of the thermal resistance. IEC 60228, Conductors of insulated cables. IEC 60949, Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects. G. J. Anders, Rating of Electric Power Cables: Ampacity Computations for Transmission, Distribution, and Industrial Applications, IEEE Press. J. H. Neher and M. H. McGrath, “The Calculation of the Temperature Rise and Load Capability of Cable Systems,” AIEE Transactions, 1957. CIGRE TB 272, Large cross-sections and composite screens design.