Voltage Drop Calculator
Voltage Drop Calculator
Draw the single-line diagram — from the utility or the transformer down to the panels, breakers, cables, motors and loads — and calculate the voltage drop at every bus and load against the PEC limits. Single-phase, three-phase, or both.
How to use the calculator
- Place equipment. Pick a tool from the toolbar, then click on the canvas. Every system starts at a Utility source or a Generator. For a house tapping the utility's secondary line, either draw the utility transformer, or set the Utility source to 1φ 3-wire 0.23 kV and enter the fault current at the tap.
- Connect. Drag from one terminal dot to another. Cables have length and impedance from the PEC conductor table; connectors are zero-impedance jumpers, for example between a panel and a load drawn at the panel.
- Single-phase branches. Select the cable that starts the branch and set its Phase tap: A-N for 115 V off a 230/115 V secondary or 230 V off a 400/230 V system, A-B for 230 V line-to-line.
- Feeders and branches. Each cable counts toward the PEC feeder or branch limit. Auto decides from the drawing; set Counts as to Utility side for a service drop.
- Run. Click an empty part of the canvas for the study settings, then press Run voltage drop.
Method notes. Effective-Z method of the PEC 2017 Table 10.1.1.9 notes, \(\Delta V = k\,I\,(R\cos\theta + X\sin\theta)\), with the exact IEEE Std 141 formula worked alongside. Loads are added as real and reactive power; single-phase loads on three-phase or 3-wire feeders are taken as spread evenly over the phases. Ampacity from PEC Table 3.10.1.16 with ambient, grouping and termination limits; resistance corrected to the conductor temperature.
Getting started
Load a template from the Template list, or press New and start with a Utility source or a Generator. Pick an element from the toolbar and click on the canvas to place it. Every diagram needs one source and at least one load or motor.
Connecting
Drag from one terminal dot to another, or choose the Cable or Connector tool and click the two elements you want to join. The wire tool stays on until you press Esc. Cables have length and impedance from the PEC conductor table; connectors are zero-impedance jumpers.
A breaker or switch has a line terminal at the top and a load terminal at the bottom. Breakers, switches and connectors add no drop.
Single-phase branches
Select the cable that starts the branch and set its phase tap: A-N for 115 V off a 230/115 V secondary or 230 V off 400/230 V, A-B for 230 V line-to-line. Leave every other link at its default.
Feeder or branch
Each cable counts toward the PEC feeder or branch-circuit limit. Auto calls a cable a branch circuit when no other cable is beyond it, and a feeder otherwise; cables above 1 kV are utility side. Set "Counts as" to Utility side for a service drop or secondary line, which the PEC limits do not cover.
Editing and tidying
Click any element or link to edit it in the panel on the right. Drag a segment of a selected link to re-route it, and drag the round handle at either end to reconnect it to another terminal. Delete removes the selection, Ctrl+Z and Ctrl+Y undo and redo, Ctrl+D duplicates and Esc cancels. Drag empty canvas to pan and use the mouse wheel to zoom.
Running the study
Click an empty part of the canvas to set the method, ambient temperature and limits, then press Run voltage drop. Every bus, panel, load and motor is tagged with its voltage in percent of nominal, and every cable with its drop; tags that fail a check show in red. Hover a tag for details. The results tables, the PDF report and the step-by-step working are below the editor.
Saving
Members can save diagrams to their account. Anyone can export and import JSON, download a PNG, or print the report to PDF.
Checks based on
PEC 2017 Table 10.1.1.9 notes; IEEE Std 141, Ch. 3
Both methods are worked for every branch; this choice decides which one the limits, tags, minimum sizes and summary use.
Effective Z (default): \(\Delta V = k\,I\,(R\cos\theta + X\sin\theta)\), the method in the PEC table notes and in most hand calculations.
Exact: the IEEE 141 formula, which adds the small quadrature term. The two differ by a few hundredths of a percent at normal drops and by more at large drops or low power factor.
Ambient temperature
PEC 2017 3.10.1.15(B)(2)
The temperature around the conductors. Table ampacities are for 30 °C; above that they are reduced by \(K_t = \sqrt{(T_c - T_a)/(T_c - 30)}\). It is also the starting point of the estimated conductor temperature. Use 30 to 35 °C indoors and 40 °C or more for conduits exposed on roofs or in hot ceiling spaces.
Branch circuit limit
PEC 2017 2.10.2.19(A) FPN No. 4
Largest drop allowed in a branch circuit on its own: 3 % by the PEC fine-print note.
Feeder limit
PEC 2017 2.15.1.2(A) FPN No. 2
Largest drop allowed in all the feeders on a path together — service entrance, feeders and sub-feeders: 3 % by the PEC fine-print note.
Feeder + branch limit
PEC 2017 2.10.2.19(A) FPN No. 4
Largest drop allowed from the service point to the farthest outlet: 5 % by the PEC fine-print note. The source, transformers and utility-side cables are not included.
Minimum motor voltage while starting
% of nominal at the motor terminals
The lowest voltage a motor may see while it starts. Starting torque falls with the square of voltage, so at 80 % the motor develops only 64 % of its rated starting torque. 80 % is a common design value for direct-on-line starting; use the motor or driven-equipment data where it is stricter.
Starting dip limit at other buses
Percentage points of nominal
The largest momentary fall in voltage allowed at the other buses and loads while a motor starts. Dips above a few percent cause visible lamp flicker if they repeat often; large dips can drop out contactors.
Source system
The conductors the source provides. A utility primary is normally 3φ 4-wire (13.8 or 34.5 kV). For a house tapping the utility's secondary line, use 1φ 3-wire at 0.23 kV (230/115 V) and start the diagram at the tap.
Source voltage
Nominal line-to-line voltage of the source (line-to-neutral for a 1φ 2-wire L-N source). 13.8, 34.5 or 69 kV for a utility primary, 0.23 kV for a 230/115 V secondary tap.
Infinite bus
Ignores the source impedance, so the source holds its voltage whatever the load. Usual for a utility primary feeding a small transformer, where the source drop is a few hundredths of a percent. Untick it and enter the available fault current to include the source drop, for example at a secondary-line tap.
Available fault current
Sets the source impedance used for the drop: \(Z_s = V_{LL}/(\sqrt{3}\,I_{sc})\) per phase for a three-phase source, or \(V/(2\,I_{sc})\) per conductor for a single-phase source. Ask the utility for the value at your point of connection.
Source X/R
Splits the source impedance into \(R = Z/\sqrt{1+(X/R)^2}\) and \(X = R\,(X/R)\). Distribution feeders are typically 5 to 15; a secondary-line tap is closer to 1 to 3.
Source voltage, % of nominal
The no-load voltage the source holds, as a percentage of nominal. Every bus voltage starts from it. Use 100 % to measure drop alone, or the utility's actual voltage (for example 105 % at light load or 95 % at the end of a long feeder) to see the voltage the equipment will get. The PEC drop checks are not affected.
Generator status
Out of service removes the generator. A generator in service is a source: to model a transfer switch, give the utility and the generator their own switches and close only one.
Generator system
The conductors the generator provides: 3φ 4-wire for a three-phase genset with neutral, or a single-phase arrangement for a portable unit.
Generator voltage
Rated line-to-line voltage. The generator is treated as holding this voltage at its terminals (its own regulation is not included).
Transformer type and connection
Sets the secondary system: a centre-tapped single-phase unit gives 1φ 3-wire (230/115 V); Dyn11, YNyn0 and Yyn0 give 3φ 4-wire; Dd0 and YNd11 give 3φ 3-wire.
Primary connection
For a single-phase unit on a three-phase primary: across a line and neutral (e.g. 7.97 kV on 13.8 kV) or across two lines. It only labels the drawing; primary loading is taken as spread over the phases.
Rated primary voltage
Voltage across the primary winding: 7.97 kV for a unit connected line-to-neutral on 13.8 kV, 34.5 kV for one connected line-to-line on 34.5 kV. The tap is assumed set so the no-load secondary is at nominal.
Rated secondary voltage
Line-to-line secondary voltage; for a centre-tapped unit, the full winding (0.23 kV for 230/115 V, 0.24 kV for 240/120 V). This is the nominal voltage of everything downstream.
Impedance %Z
Transformer nameplate
The nameplate percent impedance. It sets the drop inside the transformer:
\[ \Delta V\% = 100\,I_{pu}\,(R_{pu}\cos\theta + X_{pu}\sin\theta) \]
Small pole-mounted units are typically 1.5–3 %.
Transformer X/R
Splits %Z into \(R_{pu} = Z_{pu}/\sqrt{1+(X/R)^2}\) and \(X_{pu} = R_{pu}\,(X/R)\). Small distribution transformers are about 1 to 3, so their resistance gives much of the drop at high power factor.
Secondary conductors
For a 2-wire unit: two line conductors (e.g. 230 V L-L) or a line and a grounded neutral (230 V L-N).
Breaker status
Closed breakers have zero impedance. An open breaker disconnects everything downstream; those loads are left out.
Frame and trip rating
Frame size (AF) and trip rating (AT), shown on the drawing and in the report. They do not enter the voltage drop.
Switch status
Closed switches have zero impedance; an open switch disconnects the downstream side. Use two switches to model a transfer switch between utility and generator.
Motor rating
Rated output in hp or kW. The electrical input is \(S = P_{out}/(\eta\cos\varphi)\), with 1 hp = 0.746 kW. Split-type and window aircons, pumps and compressors are motors.
Quantity
Number of identical motors at this point. Their kVA adds; for the starting check they are taken as starting together.
Connection
Auto uses the bus as it is: all phases on a three-phase bus, line-to-line on a 230 V L-L or 230/115 V bus, line-to-neutral on an L-N bus. Choose L-L or L-N to place a single-phase load on a three-phase or 3-wire bus; it only changes the load current shown, because feeders share single-phase loads evenly over the phases.
Efficiency and power factor
Convert the rated output into input kVA, \(S = P/(\eta\cos\varphi)\), and split it into real and reactive power. Small single-phase motors are about 0.70–0.85; three-phase motors from 7.5 kW up about 0.88–0.93.
Locked-rotor multiple
Starting current ÷ running current
How many times the running current the motor draws at the instant of starting at full voltage. Direct-on-line induction motors draw 5 to 7 times; inverter aircons and soft starters much less. Use \(LRA/FLA\) from the nameplate where you have it.
Starting power factor
At locked rotor
The power factor of the starting current. It is low, so the reactance matters more while starting than in normal running. Typical 0.2 to 0.4, lower for large motors.
Load amount
The load in kVA, kW or amperes. For amperes, \(S = m\,V\,I/1000\) with \(m = \sqrt{3}\) on a three-phase bus. For a panel sized by a load schedule, enter the demand kVA. A load placed on a panel bus can stand for that panel's other circuits.
Power factor
Lagging
Splits the load into real and reactive power. The drop depends on it through \(R\cos\theta + X\sin\theta\). PEC Table 10.1.1.9 lists effective Z at 0.85, a common default for mixed loads.
Cable or connector
A cable has length and impedance and its drop is calculated. A connector is a zero-impedance jumper, for example between a panel and a breaker mounted in it, or a load drawn right at its panel.
Phase tap
Leave as "same" for ordinary links. Set it on the link that starts a branch with fewer conductors: A-N for 230 V from a 400/230 V system or 115 V from a 230/115 V secondary, A-B for 230 V line-to-line from a 230/115 V secondary or a three-phase system. The tap sets the circuit used for the drop:
| Circuit | I | ΔV |
|---|---|---|
| 3φ | \(S/\sqrt{3}V_{LL}\) | \(\sqrt{3}\,I\,Z_{eff}\) |
| 1φ 3-wire | \(S/V_{LL}\) | \(2\,I\,Z_{eff}\) |
| 1φ L-L | \(S/V_{LL}\) | \(2\,I\,Z_{eff}\) |
| 1φ L-N | \(S/V_{LN}\) | \(2\,I\,Z_{eff}\) |
Counts as
PEC 2017 2.10.2.19(A) FPN No. 4; 2.15.1.2(A) FPN No. 2
Which PEC limit the cable counts toward.
- Auto: above 1 kV, utility side; otherwise a branch circuit if no other cable is downstream, else a feeder.
- Utility side: service drop and secondary line up to the service point. Shown in the drop from the source, not counted in the PEC limits.
- Feeder: service entrance, feeders and sub-feeders; together not more than 3 %.
- Branch: the final circuit to the outlet or equipment; not more than 3 %, and feeder + branch not more than 5 %.
Load along the cable
All at the far end (default, conservative): the whole downstream current flows over the full length. Right for a feeder or a circuit to one appliance.
Spread evenly: for a branch with outlets or lights spaced along the run. The current falls off along the cable, so the drop at the last outlet is half the lumped value — the cable is calculated with an effective length \(L_{eff} = L/2\). Ampacity is still checked on the full current.
Length and parallel sets
One-way route length in metres; \(k\) already counts the return conductor. Parallel sets divide R and X and multiply the ampacity: \(R = r\,L/(1000\,n)\).
Conductor material and installation
PEC 2017 Table 10.1.1.9
Selects the table column: copper or aluminium, in PVC, aluminium or steel conduit. Steel conduit raises the reactance by about 25 %. Overhead uses the PVC-conduit values; open-wire and triplex conductors have more reactance, so use Custom R / X with the conductor's own data for those.
Conductor size
PEC 2017 Table 10.1.1.9
Area of one conductor in mm². Common sizes and AWG equivalents: 2.0 (14), 3.5 (12), 5.5 (10), 8.0 (8), 14 (6), 22 (4), 30 (2), 38 (1), 50 (1/0), 60 (2/0), 80 (3/0), 100 (4/0). The panel below the fields shows R and X used.
Custom R and X
Per-conductor resistance and reactance in Ω/km at operating temperature, from the manufacturer. No temperature correction is applied. Cables in conduit and triplex are about 0.08–0.10 Ω/km reactance; open wire on racks 0.3–0.4 Ω/km.
Ampacity (custom)
A per conductor
Allowable current of one conductor from its data sheet. Leave blank to skip the ampacity check for this cable.
Insulation rating
PEC 2017 Table 3.10.1.16
Conductor temperature rating: 60 °C for TW, 75 °C for THW, 90 °C for THHN and THWN-2. Ampacity is first taken from this column and corrected for ambient and grouping; the estimated conductor temperature is capped at it.
Termination rating
PEC 2017 1.10.1.14(C)
Temperature rating of the breaker and lug terminals. The ampacity cannot exceed the table value in this column. Unless marked otherwise, circuits of 100 A or less (and sizes up to 38 mm²) are limited to 60 °C and larger ones to 75 °C.
Current-carrying conductors in raceway
PEC 2017 Table 3.10.1.15(B)(3)(a)
Above three, the ampacity is reduced: 4–6 to 80 %, 7–9 to 70 %, 10–20 to 50 %, 21–30 to 45 %, 31–40 to 40 %, over 40 to 35 %. A neutral carrying only unbalanced current and the grounding conductor are not counted. Not applied to overhead runs.
Conductor temperature
PEC 2017 Table 10.1.1.9 note
Resistance is corrected from the table temperature: \(R_T = R_{75}[1 + \alpha(T - 75)]\), \(\alpha = 0.00323\) Cu, \(0.00330\) Al.
- 75 °C table: no correction; conservative for lightly loaded runs.
- Estimate (default): \(T = T_a + (T_c - T_a)(I/I_z)^2\), with \(I_z\) the corrected ampacity at the insulation rating.
- Enter: a temperature you have measured or calculated.
Method
- Effective-Z method (PEC 2017 Table 10.1.1.9 notes): \(\Delta V = k\,I\,(R\cos\theta + X\sin\theta)\), \(k = 2\) single-phase, \(\sqrt{3}\) three-phase (line-to-line). Exact IEEE Std 141 formula worked alongside; the study settings choose which one the checks use.
- Loads are taken at nominal voltage (constant current) and added as P and Q. Single-phase loads on three-phase or 1φ 3-wire feeders are spread evenly over the phases; the neutral of a balanced 3-wire circuit carries no current.
- Radial systems only: one source per network, no closed loops. Open a switch to choose between utility and generator.
- Breakers, switches and connectors have zero impedance. Open ones disconnect everything downstream.
Sources and transformers
- Utility: infinite bus (no drop), or a source impedance from the available fault current and X/R. The source voltage sets the starting voltage (100 % by default).
- Generator: holds its rated voltage; its own regulation is not modelled.
- Transformer: per-unit drop from %Z and X/R; the tap is assumed set so the no-load secondary is at nominal. A single-phase transformer on a three-phase primary loads the primary evenly.
Cables
- R and X from PEC 2017 Table 10.1.1.9 (600 V, three single conductors in conduit, 60 Hz, 75 °C). Overhead uses the PVC-conduit values; use Custom R / X for open-wire or triplex conductors.
- Resistance corrected to the conductor temperature: \(R_T = R_{75}[1 + \alpha(T-75)]\); estimated temperature \(T = T_a + (T_c - T_a)(I/I_z)^2\) by default.
- Ampacity from PEC 2017 Table 3.10.1.16 at the insulation column × ambient factor × grouping factor × sets, limited by the termination column (1.10.1.14(C)).
- Limits (PEC fine-print notes): branch 3 %, feeders 3 %, feeder + branch 5 %. Source, transformers and utility-side cables are not counted.
Motor starting
- Each motor started on its own with the other loads running; its current becomes the locked-rotor multiple × running kVA at the starting power factor. Effective-Z method.
Results
Checks at each load
Cables
Voltage at each bus
Motor starting
Step-by-step computation
For preliminary design and checking only. Results are based on the data you enter and typical conductor data from the PEC. The PEC voltage drop limits are fine-print recommendations. Verify against utility service voltages, transformer test reports and manufacturer data. References: Philippine Electrical Code Part 1 (2017) Table 10.1.1.9 and Table 3.10.1.16; IEEE Std 141 (Red Book), Chapter 3.