Voltage Drop Calculator

Voltage Drop Calculator

Draw the single-line diagram — from the utility or the transformer down to the panels, breakers, cables, motors and loads — and calculate the voltage drop at every bus and load against the PEC limits. Single-phase, three-phase, or both.

How to use the calculator
  1. Place equipment. Pick a tool from the toolbar, then click on the canvas. Every system starts at a Utility source or a Generator. For a house tapping the utility's secondary line, either draw the utility transformer, or set the Utility source to 1φ 3-wire 0.23 kV and enter the fault current at the tap.
  2. Connect. Drag from one terminal dot to another. Cables have length and impedance from the PEC conductor table; connectors are zero-impedance jumpers, for example between a panel and a load drawn at the panel.
  3. Single-phase branches. Select the cable that starts the branch and set its Phase tap: A-N for 115 V off a 230/115 V secondary or 230 V off a 400/230 V system, A-B for 230 V line-to-line.
  4. Feeders and branches. Each cable counts toward the PEC feeder or branch limit. Auto decides from the drawing; set Counts as to Utility side for a service drop.
  5. Run. Click an empty part of the canvas for the study settings, then press Run voltage drop.

Method notes. Effective-Z method of the PEC 2017 Table 10.1.1.9 notes, \(\Delta V = k\,I\,(R\cos\theta + X\sin\theta)\), with the exact IEEE Std 141 formula worked alongside. Loads are added as real and reactive power; single-phase loads on three-phase or 3-wire feeders are taken as spread evenly over the phases. Ampacity from PEC Table 3.10.1.16 with ambient, grouping and termination limits; resistance corrected to the conductor temperature.

Start with a Utility source or load a template. Pick a tool and click on the canvas to place it, then drag between terminal dots to connect.

For preliminary design and checking only. Results are based on the data you enter and typical conductor data from the PEC. The PEC voltage drop limits are fine-print recommendations. Verify against utility service voltages, transformer test reports and manufacturer data. References: Philippine Electrical Code Part 1 (2017) Table 10.1.1.9 and Table 3.10.1.16; IEEE Std 141 (Red Book), Chapter 3.