Electrical Engineering · Question Bank

Alternators

63 of 157 questions match · page 3 of 4. Answer in your head first, then check the solution.

✕ Clear filters
#41📜 EE Board April 1989📘 1001 RojasMedium
Problem 611: There are two alternators, 100 kW, 3-phase in parallel are driven by shunt motors whose speed-load characteristics are as follows: Alternator No.1, no-load speed 600 rpm and the full-load speed 530 rpm, while alternator No. 2, no-load speed 590 rpm and full-load speed 550 rpm. For what load will the alternator divide the load equally?
A62.45 kW
B68.78 kW
C67.54 kW
D64.67 kW
#42📜 EE Board April 1989📘 1001 RojasMedium
Problem 612: There are two alternators, 100 kW, 3-phase in parallel are driven by shunt motors whose speed-load characteristics are as follows: Alternator No.1, no-load speed 600 rpm and the full-load speed 530 rpm, while alternator No. 2, no-load speed 590 rpm and full-load speed 550 rpm. What is the greatest load that can be delivered without overloading either alternator?
A171.43 kW
B168.78 kW
C177.54 kW
D164.67 kW
#43📜 EE Pre-Board August 2012📘 PowerhouseMedium
The pitch factor for third harmonic in an alternator having 18 slots per pole and coil span 5/6 of pole pitch is _.
A0.707
B0.259
C0.966
D1
#44📜 EE Pre-Board August 2012📘 PowerhouseEasy
Calculate the average voltage generated in a six turn full pitch coil of a 60 cycle alternator if the flux per pole is \(7.2 \times 10^{5}\) maxwells.
A4.32 V
B23.4 V
C17.30 V
D10.37 V
#45📜 EE Pre-Board March 2013📘 PowerhouseHard
A three-phase, 60 Hz wye-connected wound rotor synchronous generator rated 10 kVA, 230 V has a synchronous reactance of 1.2 ohm per phase and an armature resistance of 0.5 ohm per phase. Calculate the percent regulation at full load with 0.8 lagging power factor.
A18.3%
B20.8%
C21.8%
D22.5%
#46📜 EE Pre-Board March 2013📘 PowerhouseEasy
For a coil having a span of 2/3 of pole pitch, the coil span factor is
A0.8
B0.866
C0.786
D0.966
#47📜 EE Pre-Board August 2013📘 PowerhouseMedium
The pitch factor for 3rd harmonic in an alternator having 18 slots per pole and coil span 5/6 of pole pitch is
A0.707
B0.253
C0.966
D1
#48📜 EE Pre-Board August 2013📘 PowerhouseMedium
A 6.6 kV Y-connected, 3-phase alternator has a synchronous reactance of 6 Ω per phase and a negligible resistance At a certain field current, the armature is known to induce 5.8 kV per phase. Calculate the maximum power that can be developed by the alternator at this excitation.
A12 MW
B10 MW
C9.8 MW
D11 MW
#49📜 EE Pre-Board March 2014📘 PowerhouseMedium
A three-phase alternator has 6 slots per pole per phase. Determine the distribution factor.
A0.977
B0.956
C0.963
D0.948
#50📜 EE Pre-Board August 2014📘 PowerhouseMedium
For a 36-slot 4-pole three phase full-pitch distributed winding, what is the percent reduction in the generated voltage?
A4
B3
C6
D5
#51📜 EE Pre-Board March 2015📘 PowerhouseEasy
A winding is short pitched by 60 degrees electrical. Its pitch factor is:
A0.5
B0.707
C0.966
D0.866
#52📜 EE Pre-Board August 2015📘 PowerhouseMedium
Two exactly similar turbo-alternators are rated 5 MW each. They are running in parallel. The speed load characteristics of the driving turbines are such that the frequency of alternator one drops uniformly from 60 Hz on no-load to 57.5Hz on full-load, that of alternator two from 60 Hz to 58 Hz. How will two machines share a load of 8,000 kW?
A3,556 kW, 4,444 kW
B4,000 kW, 4,000 kW
C3,500 kW, 4500 kW
D3,636 kW, 4,364 kW
#53📜 EE Pre-Board March 2016📘 PowerhouseEasy
In a 10-pole synchronous machine, 20 electrical degrees are equivalent to how many mechanical degrees?
A2
B8
C4
D10
#54📜 EE Pre-Board March 2016📘 PowerhouseEasy
Calculate the average voltage generated in a six-turn full-pitch coil of a 25-cycle alternator if the flux per pole is \(7.2 \times 10^{5}\) maxwells.
A7.4 V
B8.64 V
C1.08 V
D4.32 V
#55📜 EE Pre-Board August 2017📘 PowerhouseHard
A two-pole, three-phase, 50 Hz star connected ac generator has 9 slots/pole and 6 conductors/slot. What is the flux per pole if the open circuit terminal voltage is 1,100 volts? Take the coil span as unity.
A0.166 Wb
B0.0956 Wb
C0.287 Wb
D0.331 Wb
#56📜 EE Pre-Board August 2017📘 PowerhouseEasy
A 500 kVA alternator operates at 80% of full load with an efficiency of 92 percent. If the load power factor is 0.8, calculate the total loss.
A27.83 kW
B32.0 kW
C34.78 kW
D25.6 kW
#57📜 EE Pre-Board August 2017📘 PowerhouseEasy
A three-phase, wye-connected, 6.25 kVA, 220-volt synchronous generator has a reactance of 8.4 ohms per phase. Using the rated kVA and voltage as base values, determine the per unit reactance.
A0.627 pu
B0.362 pu
C1.085 pu
D1.879 pu
#58📜 EE Pre-Board August 2017📘 PowerhouseEasy
A two-pole alternator is running at 1,500 rpm. What is the angular velocity?
A314.2 rad/s
B78.5 rad/s
C157.1 rad/s
D25 rad/s
#59📜 EE Pre-Board March 2018📘 PowerhouseEasy
Calculate the effective voltage in one phase of an alternator, given the following particulars: f = 60 cps; turns per phase N = 240; flux per pole = \(2.08 \times 10^{6}\) maxwells.
A1,330v
B2,304v
C1,225v
D2,122v
#60📜 EE Pre-Board March 2018📘 PowerhouseHard
A three-phase 60 Hz wye-connected wound rotor synchronous generator rated at 10 kVA, 230V has a synchronous reactance of 1.2 ohm per phase and an armature resistance of 0.5 ohm per phase. Calculate the percent regulation at full-load with 0.8 lagging power factor.
A18.3%
B20.8%
C21.8%
D22.5%