Electrical Engineering · Question Bank

Power Factor Corrections

23 questions · page 1 of 2. Answer in your head first, then check the solution.

#1📜 EE Pre-Board August 2012📘 PowerhouseMedium
A load of 10,000 kVA, 80% lagging is connected to a 13,200 V line. How much capacitive reactive power is needed to correct the power factor to 97% lagging?
A3,995 kVAR
B3,138 kVAR
C5,156 kVAR
D2,547 kVAR
#2📜 EE Pre-Board March 2013📘 PowerhouseEasy
Which of the following is used in power factor correction?
AInduction motor
BLong transmission line
CSynchronous motor
DVoltage regulator
#3📜 EE Pre-Board March 2013📘 PowerhouseMedium
A 1-phase, 220-V 50-A induction motor draws 10 kW of power. A 1-phase, 8-kVA synchronous motor is placed parallel with it in order to adjust the power factor to unity. What must be the power factor of the synchronous motor?
A0.80 leading
B0.82 leading
C0.84 leading
D0.86 leading
#4📜 EE Pre-Board August 2013📘 PowerhouseMedium
A capacitor is placed in parallel with two inductive loads, one of 20 A at 30° lagging and another one of 40 A at 60° lagging. What must be the current in the capacitor so that the total current from the source shall be at unity power factor?
A44.64 A
B36.84 A
C48.36 A
D38.32 A
#5📜 EE Pre-Board August 2013📘 PowerhouseMedium
A 50 hp, 440 v, 60 HZ, 3-phase motor operates at full-load with an efficiency of 89% and power factor of 0.85 lagging. Determine the capacitance in μf per phase of wye-connected capacitor bank to be connected across the motor terminals to improve the power factor to 0.95 lagging.
A148
B167
C188
D210
#6📜 EE Pre-Board March 2014📘 PowerhouseHard
A factory works at 400 kW, 0.7 pf lagging. A 200 hp synchronous motor is connected to the plant to correct the pf to 75% lagging. What should be the pf of the synchronous motor?
A80%
B89%
C91%
D95%
#7📜 EE Pre-Board March 2014📘 PowerhouseMedium
A 10 HP, 230 v, 60 Hz three-phase motor has an efficiency of 90% and pf of 0.85 lagging. What is the capacitance per phase in microfarads to be connected in parallel with the motor correct the power factor to unity?
A258 μF
B155 μF
C25.8 μF
D15.5 μF
#8📜 EE Pre-Board March 2014📘 PowerhouseMedium
A 2.3 kV three-phase system supplies a 120 kW, 0.6 p.f. lagging balanced load. Determine the capacitance in each phase of a wye-connected capacitor bank to adjust the power factor to 0.90 lagging.
A51.1 μF
B52.2 μF
C62.5 μF
D78.2 μF
#9📜 EE Pre-Board March 2014📘 PowerhouseEasy
A single – phase load on 220 v takes 5 kW at 0.6 lagging power factor. Find the kVAR size of capacitor, which may be connected in parallel with this motor to bring the resultant power factor to unity.
A6.64
B7.32
C8.66
D6.26
#10📜 EE Pre-Board August 2014📘 PowerhouseMedium
A 400-volt, 50Hz star connected induction motor takes a line current of 50 amperes at a p.f of 0.8 lagging. Three mesh connected capacitors are connected to raise the p.f to 0.9. Find the value of each capacitor in microfarads.
A146.7
B48.9
C16.3
D24.5
#11📜 EE Pre-Board August 2014📘 PowerhouseEasy
It is desired to correct the 2,400 – KVA 0.65 Lagging power factor load in a plant unity by the installation of a synchronous condenser. Calculate the KVA rating of the latter.
A2,400
B1,825
C1,560
D1,960
#12📜 EE Pre-Board March 2015📘 PowerhouseHard
Two single-phase transformer are each rated 75 KVA are connected in V or open delta to serve a 3-phase load of 120 KW at 0.80 power factor lagging. Determine the size in KVAR of the capacitor needed to prevent overloading of the transformers.
A40.25
B41.28
C45.24
D43.5
#13📜 EE Pre-Board August 2015📘 PowerhouseEasy
A 50-MVA, 11-kV, 3-phase alternator supplies full load at a lagging power factor of 0.7. What would be the percentage increase in earning capacity if the power factor is increased to 0.95?
A26.32
B6.92
C12.76
D35.71
#14📜 EE Pre-Board March 2016📘 PowerhouseEasy
The capacitors of power factor correction are rated in terms of
AKV
BKW
CKVA
DKVAR
#15📜 EE Pre-Board March 2016📘 PowerhouseMedium
The power factor of a 20 MW, 13.2 kV, 3Φ motor is corrected to 0.9 by a 230 μF capacitor (per phase, wye). What is its initial power factor?
A0.628
B0.965
C0.765
D0.828
#16📜 EE Pre-Board March 2017📘 PowerhouseEasy
In an ac circuit, a low value of KVAR compared with KW indicates
Amaximum load current
Blow efficiency
Chigh power factor
Dunity power factor
#17📜 EE Pre-Board March 2017📘 PowerhouseMedium
A 12 KVA load A operating at 0.70 p.f. lagging and a 10 KVA load B operating at 0.80 p.f. lagging are connected in parallel and supplied by a 440 v, 60 Hz generator. Determine the system power factor.
A0.767
B0.727
C0.747
D0.787
#18📜 EE Pre-Board August 2017📘 PowerhouseMedium
A 400-volt, 50 Hz star connected induction motor takes a line current of 50 amperes at a p.f. of 0.8 lagging. Three mesh (delta) connected capacitors are connected to raise the p.f. to 0.9. Find the value of each capacitor in microfarads.
A146.7 μF
B48.9 μF
C84.7 μF
D16.3 μF
#19📜 EE Pre-Board August 2017📘 PowerhouseMedium
Two single-phase transformers each rated 75 kVA are connected in V or open delta to serve a three-phase load of 120 kW at 0.80 power factor lagging. To prevent overloading of the transformers, determine the size of the capacitor in kVAR.
A49.75 kVAR
B90 kVAR
C40.25 kVAR
D28.4 kVAR
#20📘 EE Pocket Reviewer RojasEasy
Other than using capacitors, power factor improvement can also be achieve using which of the following machines?
AA synchronous motor
BA synchronous converter
CA squirrel-cage induction motor
DAny of these

More Electrical Engineering topics