Electrical Engineering · Question Bank

Transformers

61 of 258 questions match · page 1 of 4. Answer in your head first, then check the solution.

✕ Clear filters
#1📘 1001 RojasEasy
Problem 613: The maximum flux density in the core of a 3000/240-V, 50 Hz single-phase distribution transformer is 1.25 Tesla. If the voltage induced per turn is 8 volts, determine the cross sectional of the core in cm².
A292
B375
C288
D362
#2📘 1001 RojasEasy
Problem 614: The net cross section of a transformer is 20 square inches. The maximum flux density is 11 kilogausses. The frequency is 60 Hz. If there are 1,000 turns in the primary, determine the primary induced emf.
A3780 V
B3945 V
C3590 V
D3850 V
#3📘 1001 RojasEasy
Problem 615: Calculate the total magnetic flux in a 60-cycle transformer in which the induced emf per turn of the winding is equal to 2 V.
A7.50 mWb
B7.02 mWb
C7.50 mWb
D7.42 mWb
#4📜 EE Board March 1998📘 1001 RojasEasy
Problem 626: A 13.8 kV/480 V, 10 MVA three-phase transformer has 5% impedance. What is the impedance in ohms referred to the primary?
A0.952 ohm
B0.03 ohm
C5.125 ohms
D9.01 ohms
#5📘 1001 RojasEasy
Problem 658: A 20-kVA, 500-V load is to be supplied by an ideal step-up autotransformer from a 400-V source. Find the current in the common winding.
A30 A
B40 A
C50 A
DNone of these
#6📜 EE Board June 1990📘 1001 RojasEasy
What should be the kVA rating of each two transformers in an open-delta bank when the three-phase balanced load is $290.4$ kVA?
A155.60 kVA
B173.40 kVA
C150.25 kVA
D167.66 kVA
#7📜 EE Board April 1981📘 1001 RojasEasy
A V or open delta connected transformer bank, composed of two identical units serves a balanced $3$-phase load of $16$ kVA at $230$ volts. Solve for the minimum size in kVA of the transformers needed.
A8 kVA
B9.24 kVA
C16 kVA
D8.25 kVA
#8📜 EE Board April 1986📘 1001 RojasEasy
A V (open delta) connected transformer bank serves a balanced $3$-phase load of $40$ kVA at $230$ V and $0.866$ pf lagging. Solve for the minimum kVA of each transformer needed to accommodate the load without overloading.
A25
B24
C23
D20
#9📜 EE Board April 1985📘 1001 RojasEasy
Two single-phase distribution transformers are banked in V (open delta). If each transformer is rated $37.5$ kVA, solve for the maximum $3$-phase load that the bank can carry without overloading, considering that the load has a power factor of $0.85$ lagging.
A52.5 kW
B49.5 kW
C53.6 kW
D55.2 kW
#10📜 EE Board October 1986📘 1001 RojasEasy
The Utility Company supplies two single-phase transformers banked in open delta. If each transformer is rated $75$ kVA capacity, what is the maximum $3$-phase load in kilowatts that the bank can carry without suffering overload considering that the load has a lagging power factor of $0.80$.
A104 kW
B112 kW
C130 kW
D114 kW
#11📜 EE Board October 1980📘 1001 RojasEasy
Two identical $1$-phase transformers connected in open delta will serve a $3$-phase motor load of $250$ hp, $0.70$ pf lagging, $0.90$ efficiency. Solve for the minimum size in kVA of each transformer required to serve the load without overloading.
A150.33
B170.91
C160.43
D185.15
#12📜 EE Board June 1990📘 1001 RojasEasy
Two single-phase transformers in an open-delta bank served a three-phase balanced load of $290.4$ kVA. If a third transformer is added for delta operation, what percent increase in load does this represent?
A73.2%
B84.6%
C80.5%
D79.4%
#13📜 EE Board October 1983📘 1001 RojasEasy
Three-single phase transformers each rated $75$ kVA are banked in delta and supplying a $3$-phase load drawing $160$ kVA at $0.8$ lagging power factor. If one transformer is removed for repairs, solve for the amount of overloading of the remaining units.
A30 kVA
B10 kVA
C20 kVA
D25 kVA
#14📜 EE Board October 1991📘 1001 RojasEasy
What should be the turns ratio of a three phase transformer to transform $10000$ kVA from $230$ kV to $4160$ V if the transformer is to be connected $\Delta - Y$?
A94
B98
C96
D97
#15📘 1001 RojasEasy
A bank of three $50:1$ single-phase transformers connected Y-$\Delta$ is used to step down the HV transmission line rated $138$ kV. Determine the magnitude of the step down voltage.
A126 kV
B6.90 kV
C138.55 kV
D159.35 kV
#16📜 EE Board October 1997📘 1001 RojasEasy
A power transformer rated $50000$ kVA, $34.5 \text{ kV}/13.8 \text{ kV}$ is connected wye-grounded primary and delta on the secondary. Determine the full load phase current on the secondary side.
A2092 A
B1725 A
C1449 A
D1208 A
#17📜 EE Board October 1998📘 1001 RojasEasy
A $69/13.8$ kV, $10$ MVA three-phase transformer is connected wye-grounded delta. What is the kV rating of the secondary winding?
A7.97
B15
C23.9
D13.8
#18📜 EE Board October 1997📘 1001 RojasEasy
A power transformer rated $50000$ kVA, $34.5 \text{ kV}/13.8 \text{ kV}$ is connected wye-wye. What are the line currents at full load?
A525.2 A, 1725.4 A
B836.7 A, 2092 A
C483.1 A, 1207.7 A
D1449.3 A, 3623.2 A
#19📜 EE Pre-Board August 2012📘 PowerhouseEasy
If the secondary terminals of a 5:1 stepdown transformer is connected to the primary of a 2:1 stepdown transformer then the total stepdown ratio of both transformers is
A2.5 : 1
B3 : 1
C10 : 1
D7 : 1
#20📜 EE Pre-Board August 2012📘 PowerhouseEasy
A transformer has a maximum efficiency of 95% at a load of 100 kW. What is the constant loss of the transformer?
A6.32 kW
B3.26 kW
C3.62 kW
D2.63 kW