A 10:1 ideal transformer has a load of 0.1μF on the secondary. What is the load capacitance, as referred to the primary?
A1μF
B10μF
C0.01μF
D0.001μF
#122📜 EE Pre-Board August 2015📘 PowerhouseEasy
A 50-kVA single-phase transformer has on full-load a copper loss of 560 watts and iron loss of 500 watts. Calculate the efficiency at 25% of full-load for a power factor of 0.8 lagging.
A92.94%
B94.92%
C93.94%
D95.92%
#123📜 EE Pre-Board August 2015📘 PowerhouseMedium
The core loss of a 5-kVA single-phase transformer with normal voltage applied to the primary is 75 watts. The maximum efficiency occurs 60% of full- load kVA. What is the full-load efficiency of the transformer at 0.80 power factor?
A95.16%
B93.38%
C89.52%
D91.36%
#124📜 EE Pre-Board August 2015📘 PowerhouseEasy
A power transformer rated 50MVA, 34.5kV/13.8 kV is connected wye-wye. What is the rated primary line current?
A836.7 A
B1,449.3 A
C2,091.8 A
D1,207.7 A
#125📜 EE Pre-Board March 2016📘 PowerhouseMedium
A three phase wye delta connected, 50MVA, 345/ 34.5 Kv transformer is protected by differential protection. The current transformer on the high side for differential protection is 150:5. What is the current on the secondary side of CT’s?
A3.83A
B2.53A
C4.50A
D4.83A
#126📜 EE Pre-Board March 2016📘 PowerhouseEasy
When a V-V system is converted into Δ-Δ system, increase in the capacity of the system is _____ percent.
A86.8
B73.2
C66.6
D50
#127📜 EE Pre-Board March 2016📘 PowerhouseEasy
The applied voltage in a transformer is increased by 50 % and frequency is reduced by 50 %. The maximum core flux density will become ______________.
Asame
B1.5 times
C3 times
D5 times
#128📜 EE Pre-Board March 2016📘 PowerhouseEasy
A transformer has 4 % resistance and 6 % reactance drop. Find the voltage regulation at full-load 0.8 p.f. lagging.
A6.8 %
B5.8 %
C4.8 %
D160%
#129📜 EE Pre-Board March 2016📘 PowerhouseEasy
A 13.8 kV/440 V, 50 kVA single-phase transformer has a leakage reactance of 300 ohms referred to the 13.8 kV side. Determine the per unit value of the leakage reactance on the low voltage base.
A0.305
B0.4
C0.097
D0.079
#130📜 EE Pre-Board March 2017📘 PowerhouseEasy
Compute for the core loss if the transformer consumes 75 watts when it is connected across a 240 v source and taking 1.4 A. The primary resistance is 0.25 Ω
A73.6 W
B74.65 W
C74.75 W
D74.51 W
#131📜 EE Pre-Board March 2017📘 PowerhouseEasy
The primary of transformer has 200 turns and is excited by a 240 v, 60 Hz source. What is the maximum value of the core flux?
A4.04 mWb
B4.5 mWb
C4.13 mWb
D4.32 mWb
#132📜 EE Pre-Board March 2017📘 PowerhouseEasy
A transformer has negligible resistance and a p.u. reactance of 0.1. What is its voltage regulation on full load with a leading p.f. angle of 30°?
A-10%
B10%
C5%
D-5%
#133📜 EE Pre-Board August 2017📘 PowerhouseEasy
The output current corresponding to maximum efficiency for a transformer having a core loss of 100 watts and an equivalent resistance referred to the secondary of 0.25 Ω is ________ amperes.
A10
B20
C25
D40
#134📜 EE Pre-Board August 2017📘 PowerhouseEasy
If the copper loss of a transformer at 7/8 of full load is 4,900 W, what is its full-load copper loss?
A4,288 W
B6,400 W
C5,600 W
D3,752 W
#135📜 EE Pre-Board August 2017📘 PowerhouseHard
Two transformers are connected in open delta and deliver a balanced three-phase load of 245 kW at 460 volts and a power factor of 0.707. Calculate the power delivered by the individual transformers.
A122.5 kW, 122.5 kW
B193.2 kW, 51.8 kW
C173.2 kW, 71.8 kW
D141.4 kW, 103.6 kW
#136📜 EE Pre-Board August 2017📘 PowerhouseMedium
A 20 kV/7.87 kV autotransformer has a secondary line current of 100 A. What is the current in the common winding?
A39.35 A
B60.65 A
C100 A
D139.35 A
#137📜 EE Pre-Board August 2017📘 PowerhouseMedium
Three 30:1 step-down transformers are connected Y–Δ for stepping down the 132,000 volt three-phase transmission voltage. Calculate the secondary line voltage.
A4,400 V
B7,621 V
C2,540 V
D1,467 V
#138📜 EE Pre-Board March 2018📘 PowerhouseMedium
A 20 KV/7.87 KV autotransformer has a secondary line current of 100 A. What is the current in the common winding?
A139.25 A
B100 A
C60.65 A
D39.35 A
#139📜 EE Pre-Board March 2018📘 PowerhouseEasy
Two single-phase, 25-kVA transformers are connected in an open-delta bank. Determine the maximum kW the bank can supply without overloading at 0.8 p.f. lagging.
A43.3
B34.64
C40
D50
#140📜 EE Pre-Board March 2018📘 PowerhouseEasy
Three 1:1 transformer units connected Δ/Y supply a 3-phase load from a 400 volt, 3-phase source. What is the line voltage on the load side?