Electrical Engineering · Question Bank

Transmission Lines

33 of 168 questions match · page 2 of 2. Answer in your head first, then check the solution.

✕ Clear filters
#21📜 EE Pre-Board August 2015📘 PowerhouseHard
A 3 phase, 60 Hz transposed transmission line is arranged horizontally with distances \(D_{12} = 5\) ft, \(D_{23} = 5\) ft and \(D_{13} = 10\) ft. The outside diameter of the conductors is 0.721 inch and the GMR is 0.0243 ft. Determine the capacitance per phase of the line in microfarad per kilometer.
A0.0404
B0.0304
C0.0204
D0.0104
#22📜 EE Pre-Board August 2015📘 PowerhouseHard
The capacitance per kilometer of a 3-phase belted cable is 0.3μF between the two cores with the third core connected to the lead sheath. Calculate the charging current taken by the five kilometers of this cable when connected to a 3-phase 50 Hz, 11kV supply.
A5.98A
B10.37A
C3A
D4.18A
#23📜 EE Pre-Board August 2015📘 PowerhouseHard
Find the capacitive susceptance per mile to neutral of a single-phase line operating at 60 Hz. The conductor is Partridge with an outside diameter of 0.642 inch, and spacing is 20 ft between centers.
A\(2.55 \times 10^{-6}\) mho/mi to neutral
B\(2.55 \times 10^{-4}\) mho/mi to neutral
C\(5.10 \times 10^{-6}\) mho/mi to neutral
D\(5.10 \times 10^{-4}\) mho/mi to neutral
#24📜 EE Pre-Board August 2015📘 PowerhouseHard
Estimate the distance over which a load of 150 MW at a power factor of 0.8 lagging can be delivered by a three phase transmission line having conductors each of resistance 0.1 ohm per kilometer. The voltage at the receiving end is to be 132 kV and the loss in the transmission is to be 5% of the power delivered.
A37.18 km
B55.77 km
C42.93 km
D74.36 km
#25📜 EE Pre-Board March 2016📘 PowerhouseHard
A conductor has four identical strands arranged in diamond configuration. Find the GMR of the conductor in terms of the radius r of each strand.
A1.6921r
B1.7037r
C1.3008r
D1.3052r
#26📜 EE Pre-Board March 2016📘 PowerhouseHard
A three phase, 60Hz, transmission line has its conductors arranged in a triangular configuration so that the two distances between conductors are 5m and the third is 8m. the conductors have an outside diameter of 250 mils. Find the inductive reactance in ohm per km per phase of the transmission line.
A0.567
B0.283
C0.586
D0.293
#27📜 EE Pre-Board March 2017📘 PowerhouseHard
A 115 kV three-phase transposed transmission line is composed of 2-ACSR 336,400 cmil, 30/7 Oriole conductor per phase with horizontal configuration: \(D_{12}\) = 7 ft, \(D_{23}\) = 7 ft, \(D_{13}\) =14 ft. The line spacing is measured from the center of the bundled conductors. The distance between the conductors of the bundle is 6 inches. The conductors have a diameter of 0.741 inch and a GMR of 0.02255 ft. Find the capacitance per phase for 20 km of the line in microfarads.
A0.13
B0.2719
C0.2889
D0.2609
#28📜 EE Pre-Board August 2017📘 PowerhouseHard
A short 3Φ transmission line with an impedance of 6 + j8 Ω per phase has sending and receiving end voltages of 120 kV and 110 kV respectively for some receiving end load at a p.f. of 0.9 lagging. Determine the sending end power factor.
A0.88 lagging
B0.90 lagging
C0.84 lagging
D0.93 lagging
#29📜 EE Pre-Board August 2017📘 PowerhouseHard
A three-phase 60 Hz transposed 230 kV transmission line has a horizontal configuration with \(D_{ab} = D\), \(D_{bc} = D\) and \(D_{ac} = 2D\). The line reactance is 0.486 ohm per km. The conductor GMR is 2.0 cm. What is the phase spacing D?
A8 m
B10 m
C12.6 m
D6.3 m
#30📜 EE Pre-Board August 2017📘 PowerhouseHard
A 3-phase, 60 Hz, 230 kV transposed transmission line is composed of two 1,272 MCM 54/19 conductors per phase with horizontal configuration. The bundle conductors are 50 cm apart, while the phase spacing between the centers of the bundles is 10 meters. If the GMR of the ACSR conductors is 0.0466 ft, find the inductive reactance in ohm/km/phase of the line.
A0.3775
B0.4386
C0.3292
D0.5054
#31📜 EE Pre-Board March 2018📘 PowerhouseHard
A three-phase 60 Hz line has flat horizontal spacing. The conductors have an outside diameter of 3.28 cm with 12 m between conductors. Determine the capacitive reactance of the line to neutral if its length is 125 miles.
A\(1.6 \times 10^{3}\) Ω
B\(202.4 \times 10^{3}\) Ω
C\(25.3 \times 10^{3}\) Ω
D\(16.2 \times 10^{3}\) Ω
#32📜 EE Pre-Board March 2018📘 PowerhouseHard
A 170-mile, 230 kV, 60 Hz, three-phase single circuit transmission line uses a triangular arrangement with 20 ft, 20 ft, and 36 ft spacing. If the line conductors have a radius of 0.0217 ft, determine the capacitive susceptance to neutral per mile.
A\(4.81 \times 10^{-6}\) mho per mile
B\(12.74 \times 10^{-8}\) mho per mile
C\(7.92 \times 10^{-6}\) mho per mile
D\(2.47 \times 10^{-6}\) mho per mile
#33📜 EE Pre-Board August 2018📘 PowerhouseHard
A single-phase transmission line having a length of 15 miles is composed of two copper conductors spaced 7 ft apart having a diameter of 0.575 inch. Determine the line to line capacitance in farad if the system frequency is 60 Hz.
A\(4.9 \times 10^{-12}\)
B\(9.8 \times 10^{-12}\)
C\(11.8 \times 10^{-9}\)
D\(118 \times 10^{-9}\)