Each conductor of a horizontally arranged two- conductor bundle line is ACSR, 1,272 MCM Pheasant. The spacing between bundle centers is 8m, 8m and 16m and between bundle conductors is 45 cm. Find the inductive reactance of the line in ohms per km per phase if GMR of each conductor is 0.0466 ft.
A0.165
B0.265
C0.365
D0.465
#42📜 EE Pre-Board August 2014📘 PowerhouseMedium
A single-phase transmission line has a total resistance of 1.5 Ω and a loop reactance of 0.3 Ω. It delivers 2 MW at 11 kV at a power factor of 0.8 lagging. Calculate the line voltage at the sending end.
A11.21kV
B11.11kV
C11.41kV
D11.31kV
#43📜 EE Pre-Board August 2014📘 PowerhouseHard
Find the capacitive susceptance per mile of single-phase line operating at 60Hz. The conductor is partridge with an outside diameter of 0.642in and spacing is 20ft. between centers.
A\(4.10 \times 10^{-6}\) mho/mile to neutral
B\(4.90 \times 10^{-6}\) mho/mile to neutral
C\(5.10 \times 10^{-6}\) mho/mile to neutral
D\(5.90 \times 10^{-6}\) mho/mile to neutral
#44📜 EE Pre-Board March 2015📘 PowerhouseHard
A three-phase transmission line of a two-conductor bundle is arranged horizontally with a spacing of 8 m between bundle centers. Each conductor is ACSR, 1,272,000 cmils Pheasant with GMR of 0.0466 ft. the spacing between conductors of bundle is 45 cm. Find the per unit series reactance of the line if its length is 160 km and base is 100 MVA, 345 KV.
A0.069 pu
B0.059 pu
C0.049 pu
D0.039 pu
#45📜 EE Pre-Board March 2015📘 PowerhouseEasy
A string insulator has 5 units. The voltage across the bottom most until is 30% of the total voltage. What is the string efficiency?
A60%
B66.67%
C75%
D83.33%
#46📜 EE Pre-Board March 2015📘 PowerhouseEasy
The capacitance reactance of a transmission line is 90,000 ohms per kilometer. Find the total capacitance reactance if the transmission line is 50 km long.
A90,000 Ω
B\(4.5 \times 10^{6}\) Ω
C180,000 Ω
D1,800 Ω
#47📜 EE Pre-Board March 2015📘 PowerhouseMedium
A load of 10 MVA, 0.8 p.f. lagging, 22 KV is served by a transmission line which has a line resistance of 3 ohms and a line reactance of 10 ohms. Solve for the sending end voltage.
A25,972 v
B28,721 v
C22,433 v
D24,214 v
#48📜 EE Pre-Board March 2015📘 PowerhouseHard
Find the capacitive susceptance per mile of a single-phase line operating at 60 HZ. The conductor is Partridge with an outside diameter of 0.642 in, and spacing is 20 ff between centers.
A\(5.10 \times 10^{-4}\) mho/mi to neutral
B\(0.1961 \times 10^{4}\) mho/mi to neutral
C\(5.10 \times 10^{-6}\) mho/mi to neutral
D\(0.1961 \times 10^{-4}\) mho/mi to neutral
#49📜 EE Pre-Board March 2015📘 PowerhouseMedium
The PTs of a 220 KV transmission line have a ratio of 132.76 KV/ 66.375 v and are connected wye-wye. A voltmeter connected line to ground reads 66 volts, what is the transmission line voltage?
A228.65 KV
B220.10 KV
C223.15 KV
D225.25 KV
#50📜 EE Pre-Board March 2015📘 PowerhouseMedium
Two No. 8 copper conductors are placed 15 cm apart with a GMR of \(1.27 \times 10^{-3}\) m. if the lenth of the line is 4 km, find the value of the line inductance.
A9.65 mH
B6.85 mH
C5.78 mH
D7.63 mH
#51📜 EE Pre-Board March 2015📘 PowerhouseHard
The conductors of a 30 km long transmission line have a triangular configuration. The conductors are placed 4 ft apart. Each conductor has 336.4 MCM ACSR and its diameter is 0.75 inch. Find the capacitive reactance per phase?
A5,389 Ω/phase
B1,354 Ω/phase
C7,712 Ω/phase
D8,261 Ω/phase
#52📜 EE Pre-Board August 2015📘 PowerhouseHard
A 3 phase, 60 Hz transposed transmission line is arranged horizontally with distances \(D_{12} = 5\) ft, \(D_{23} = 5\) ft and \(D_{13} = 10\) ft. The outside diameter of the conductors is 0.721 inch and the GMR is 0.0243 ft. Determine the capacitance per phase of the line in microfarad per kilometer.
A0.0404
B0.0304
C0.0204
D0.0104
#53📜 EE Pre-Board August 2015📘 PowerhouseHard
The capacitance per kilometer of a 3-phase belted cable is 0.3μF between the two cores with the third core connected to the lead sheath. Calculate the charging current taken by the five kilometers of this cable when connected to a 3-phase 50 Hz, 11kV supply.
A5.98A
B10.37A
C3A
D4.18A
#54📜 EE Pre-Board August 2015📘 PowerhouseEasy
A string insulator has 5 units. The voltage across the bottom most unit is 25% of the total voltage. What is the string efficiency?
A80%
B75%
C67%
D86%
#55📜 EE Pre-Board August 2015📘 PowerhouseHard
Find the capacitive susceptance per mile to neutral of a single-phase line operating at 60 Hz. The conductor is Partridge with an outside diameter of 0.642 inch, and spacing is 20 ft between centers.
A\(2.55 \times 10^{-6}\) mho/mi to neutral
B\(2.55 \times 10^{-4}\) mho/mi to neutral
C\(5.10 \times 10^{-6}\) mho/mi to neutral
D\(5.10 \times 10^{-4}\) mho/mi to neutral
#56📜 EE Pre-Board August 2015📘 PowerhouseMedium
A 34.5 kV feeder line is 5 miles long. The conductors are spaced 4-feet horizontally. The conductor is 4/0 copper with GMR of 0.01688 ft. What is the reactance?
A2.36 Ω
B6.72 Ω
C3.46 Ω
D5.16 Ω
#57📜 EE Pre-Board August 2015📘 PowerhouseEasy
The capacitive reactance of a transmission line is 90,000 ohms per kilometer. Find the total capacitive reactance if the transmission line is 60 km long.
A\(5.4 \times 10^{6}\) Ω
B1,500 Ω
C90,000 Ω
D180,000 Ω
#58📜 EE Pre-Board August 2015📘 PowerhouseHard
Estimate the distance over which a load of 150 MW at a power factor of 0.8 lagging can be delivered by a three phase transmission line having conductors each of resistance 0.1 ohm per kilometer. The voltage at the receiving end is to be 132 kV and the loss in the transmission is to be 5% of the power delivered.
A37.18 km
B55.77 km
C42.93 km
D74.36 km
#59📜 EE Pre-Board March 2016📘 PowerhouseHard
A conductor has four identical strands arranged in diamond configuration. Find the GMR of the conductor in terms of the radius r of each strand.
A1.6921r
B1.7037r
C1.3008r
D1.3052r
#60📜 EE Pre-Board March 2016📘 PowerhouseHard
A three phase, 60Hz, transmission line has its conductors arranged in a triangular configuration so that the two distances between conductors are 5m and the third is 8m. the conductors have an outside diameter of 250 mils. Find the inductive reactance in ohm per km per phase of the transmission line.