#21📜 EE Board April 1992📘 1001 RojasMedium
Problem 596: A three-phase turbo alternator has a reactance of 15 ohms and negligible resistance, the machine draws an armature current of 250 amperes at 0.8 pf lagging when running on 12,000 volts infinite busbars. If the steam admission is constant but the emf is raised by 20%, calculate the new operating pf.
A0.547
B0.586
C0.509
D0.575
#22📘 1001 RojasMedium
Problem 597: A three-phase, 20 kV, synchronous alternator has a reactance of 10 ohms and a negligible resistance. The machine draws an armature current of 150 A, 0.80 pf lagging. If the steam admission is constant and field current is adjusted raising the induced the emf by 25%, determine the value of the new armature current.
A442 A
B452 A
C421 A
D433 A
#23📜 EE Board April 1980📘 1001 RojasMedium
Problem 598: A standby Diesel generator set will have the following loads: Inductive load drawing 50 kVA at 0.8 power factor; Lighting load drawing 20 kVA at 1.0 power factor. At what power factor will the generator operate?
A0.855 lagging
B0.872 lagging
C0.821 lagging
D0.894 lagging
#24📜 EE Board April 1992📘 1001 RojasMedium
Problem 599: A 250 V, 30 Hz generator supplies power to a parallel circuit consisting of a 20 hp motor whose efficiency is 90% at 0.80 pf lagging and a second load that draws an apparent power of 7 kVA at unity pf. Determine the system reactive power.
A23.582 kVAR
B12.435 kVAR
C10.341 kVAR
D20.384 kVAR
#25📘 1001 RojasMedium
Problem 600: Two 3-\(\phi\), 4160 V, 60 Hz alternators are operated in parallel. The total load of the system is 1050 W at 75% lagging pf. If alternator A is carrying 700 kW at 80% pf lagging, determine kVAR of alternator B.
A401 kVAR
B405 kVAR
C411 kVAR
D408 kVAR
#26📜 EE Board October 1980📘 1001 RojasMedium
Problem 601: Two alternators A and B are operating in parallel supplying a load drawing 1000 kVA at 0.80 power factor lagging. If alternator A contributes 500 kVA at 0.60 power factor lagging, determine the power factor of alternator B.
A0.928 lagging
B0.852 lagging
C0.901 lagging
D0.977 lagging
#27📘 1001 RojasMedium
Problem 602: Two identical three-phase Y-connected alternators A and B share equally a load of 10 MW at 33 kV and 80% lagging pf. The synchronous reactance of each machine is 4 ohms per phase and the armature resistance is negligible. Alternator A has its field excitation adjusted to carry 125 A lagging current, what is the current supplied by alternator B?
A96 A
B97 A
C98 A
D95 A
#28📘 1001 RojasMedium
Problem 603: Alternator A (100 kVA, 3-\(\phi\), 240 V, 60 Hz, 1800 rpm) is operating in parallel with alternator B (125 kVA, 3-\(\phi\), 240 V, 60 Hz, 1800 rpm). The load of alternator A is 60 kW at 90% pf lagging and the load of alternator B is 80 kW at 70% pf lagging. Determine pf of load.
A0.775 lagging
B0.784 lagging
C0.893 lagging
D0.866 lagging
#29📘 1001 RojasMedium
Problem 604: Two 3-phase, Y-connected turbo alternators supply a load of 3000 kW at 6.6 kV and at 0.8 pf lagging. The excitation of machine A is adjusted so that it delivers 150 A at a lagging power factor, and the governors are so set that the load is shared equally between the machines. Determine the operating power factor of machine B.
A0.726
B0.792
C0.704
D0.768
#30📜 EE Board October 1981📘 1001 RojasMedium
Problem 605: Two alternators are operating in parallel supplying a common load of 4250 kW at 0.85 power factor lagging. Alternator A contributes 600 kVAR at 0.92 power factor lagging. Solve for the power factor of alternator B
A0.813 lagging
B0.834 lagging
C0.804 lagging
D0.820 lagging
#31📘 1001 RojasMedium
Problem 606: Two Y-connected alternators A and B running in parallel supply the following loads at 3.3 kV: Load 1: 800 kW at unity pf; Load 2: 600 kW at 0.8 pf lagging; Load 3: 400 kW at 0.707 pf lagging. If alternator A is adjusted to carry an armature current of 150 A at 0.85 pf lagging, what is the armature current of alternator B?
A208 A
B180 A
C200 A
D190 A
#32📘 1001 RojasMedium
Problem 607: Two AC generators running in parallel supply the following loads: 400 kW at unity pf; 500 kW at 0.9 pf lagging; 600 kW at 0.866 pf lagging. One machine is loaded to 1000 kW at a pf of 0.92 lagging, what is the operating power factor of the second machine.
A0.964 lagging
B0.921 lagging
C0.932 lagging
D0.951 lagging
#33📘 1001 RojasMedium
Problem 608: Two alternators are connected in parallel. The total load is 4250 kW at 0.85 pf lagging. Alternator A operates with a load of 2125 kW at 0.707 pf lagging. Determine the kVA load of alternator B.
A2245
B2078
C2185
D2410
#34📜 EE Board April 1988📘 1001 RojasMedium
Problem 609: Sipalay Mines, has two 3-phase, 60 Hz AC generators operating in parallel. The first unit has a capacity of 1000 kVA and the second unit has a capacity of 1500 kVA. The first is driven by a prime mover so adjusted that the frequency fall from 61 Hz at no-load to 59.6 Hz at full load. The second has a different speed-load characteristics, the frequency fall from 61.4 Hz at no-load to 59.2 Hz at full load. When these alternators are jointly delivering 2000 kW, what is the load of each generator?
A884 kW, 1116 kW
B867 kW, 1133 kW
C915 kW, 1085 kW
D804 kW, 1196 kW
#35📜 EE Board April 1989📘 1001 RojasMedium
Problem 610: Two alternators are driven by shunt motors. The shunt motors have speed-load droop characteristics of 3% and 4% respectively. The alternators are in parallel and each carrying 50 kW. There is no automatic speed-load control. An additional 50 kW is switched on. What are the resulting loads of the alternators assuming that the speed-load control of each is not adjusted?
A78.57 kW / 71.43 kW
B82.51 kW / 67.49 kW
C75 kW / 75 kW
D80.31 kW / 69.69 kW
#36📜 EE Board April 1989📘 1001 RojasMedium
Problem 611: There are two alternators, 100 kW, 3-phase in parallel are driven by shunt motors whose speed-load characteristics are as follows: Alternator No.1, no-load speed 600 rpm and the full-load speed 530 rpm, while alternator No. 2, no-load speed 590 rpm and full-load speed 550 rpm. For what load will the alternator divide the load equally?
A62.45 kW
B68.78 kW
C67.54 kW
D64.67 kW
#37📜 EE Board April 1989📘 1001 RojasMedium
Problem 612: There are two alternators, 100 kW, 3-phase in parallel are driven by shunt motors whose speed-load characteristics are as follows: Alternator No.1, no-load speed 600 rpm and the full-load speed 530 rpm, while alternator No. 2, no-load speed 590 rpm and full-load speed 550 rpm. What is the greatest load that can be delivered without overloading either alternator?
A171.43 kW
B168.78 kW
C177.54 kW
D164.67 kW
#38📜 EE Pre-Board August 2012📘 PowerhouseMedium
The pitch factor for third harmonic in an alternator having 18 slots per pole and coil span 5/6 of pole pitch is _.
A0.707
B0.259
C0.966
D1
#39📜 EE Pre-Board August 2013📘 PowerhouseMedium
The pitch factor for 3rd harmonic in an alternator having 18 slots per pole and coil span 5/6 of pole pitch is
A0.707
B0.253
C0.966
D1
#40📜 EE Pre-Board August 2013📘 PowerhouseMedium
A 6.6 kV Y-connected, 3-phase alternator has a synchronous reactance of 6 Ω per phase and a negligible resistance At a certain field current, the armature is known to induce 5.8 kV per phase. Calculate the maximum power that can be developed by the alternator at this excitation.
A12 MW
B10 MW
C9.8 MW
D11 MW