A winding is short pitched by 60 degrees electrical. Its pitch factor is:
A0.5
B0.707
C0.966
D0.866
#62📜 EE Pre-Board August 2015📘 PowerhouseMedium
Two exactly similar turbo-alternators are rated 5 MW each. They are running in parallel. The speed load characteristics of the driving turbines are such that the frequency of alternator one drops uniformly from 60 Hz on no-load to 57.5Hz on full-load, that of alternator two from 60 Hz to 58 Hz. How will two machines share a load of 8,000 kW?
A3,556 kW, 4,444 kW
B4,000 kW, 4,000 kW
C3,500 kW, 4500 kW
D3,636 kW, 4,364 kW
#63📜 EE Pre-Board March 2016📘 PowerhouseEasy
In a 10-pole synchronous machine, 20 electrical degrees are equivalent to how many mechanical degrees?
A2
B8
C4
D10
#64📜 EE Pre-Board March 2016📘 PowerhouseEasy
Calculate the average voltage generated in a six-turn full-pitch coil of a 25-cycle alternator if the flux per pole is \(7.2 \times 10^{5}\) maxwells.
A7.4 V
B8.64 V
C1.08 V
D4.32 V
#65📜 EE Pre-Board August 2017📘 PowerhouseEasy
For proper parallel operation, ac polyphase alternators must have the same ______
AkVA rating
Bpower factor
Cvoltage rating
Dspeed
#66📜 EE Pre-Board August 2017📘 PowerhouseHard
A two-pole, three-phase, 50 Hz star connected ac generator has 9 slots/pole and 6 conductors/slot. What is the flux per pole if the open circuit terminal voltage is 1,100 volts? Take the coil span as unity.
A0.166 Wb
B0.0956 Wb
C0.287 Wb
D0.331 Wb
#67📜 EE Pre-Board August 2017📘 PowerhouseEasy
A 500 kVA alternator operates at 80% of full load with an efficiency of 92 percent. If the load power factor is 0.8, calculate the total loss.
A27.83 kW
B32.0 kW
C34.78 kW
D25.6 kW
#68📜 EE Pre-Board August 2017📘 PowerhouseEasy
A three-phase, wye-connected, 6.25 kVA, 220-volt synchronous generator has a reactance of 8.4 ohms per phase. Using the rated kVA and voltage as base values, determine the per unit reactance.
A0.627 pu
B0.362 pu
C1.085 pu
D1.879 pu
#69📜 EE Pre-Board August 2017📘 PowerhouseEasy
A two-pole alternator is running at 1,500 rpm. What is the angular velocity?
A314.2 rad/s
B78.5 rad/s
C157.1 rad/s
D25 rad/s
#70📜 EE Pre-Board August 2017📘 PowerhouseEasy
At leading p.f., the armature flux in an alternator ________ the rotor flux.
Aopposes
Bis in quadrature with
Caids
Dhas no effect on
#71📜 EE Pre-Board March 2018📘 PowerhouseEasy
Calculate the effective voltage in one phase of an alternator, given the following particulars: f = 60 cps; turns per phase N = 240; flux per pole = \(2.08 \times 10^{6}\) maxwells.
A1,330v
B2,304v
C1,225v
D2,122v
#72📜 EE Pre-Board March 2018📘 PowerhouseEasy
The power factor of an alternator is determined by its
Aspeed
Bload
Cexcitation
Dprime mover
#73📜 EE Pre-Board March 2018📘 PowerhouseHard
A three-phase 60 Hz wye-connected wound rotor synchronous generator rated at 10 kVA, 230V has a synchronous reactance of 1.2 ohm per phase and an armature resistance of 0.5 ohm per phase. Calculate the percent regulation at full-load with 0.8 lagging power factor.
A18.3%
B20.8%
C21.8%
D22.5%
#74📜 EE Pre-Board March 2018📘 PowerhouseEasy
For coil having a span of 2/3 of pole pitch, the coil span factor is
A0.8
B0.866
C0.786
D0.966
#75📜 EE Pre-Board August 2018📘 PowerhouseEasy
In a 6-pole alternator how many mechanical degrees is the equivalent of 180 electrical degrees?
A60
B30
C120
D90
#76📜 EE Pre-Board August 2018📘 PowerhouseEasy
For two alternators operating in parallel, if the load shared by one of them is to be increased, its field excitation is
Ato be strengthened keeping input torque the same
Bto be weakened keeping input torque the same
Cto be kept constant but input torque should be increased
Dto be kept constant but input torque should be decreased
#77📜 EE Pre-Board August 2018📘 PowerhouseEasy
The field system of a 50 Hz alternator has a sinusoidal flux per pole of 0.1 Wb. Calculate the emf generated in one turn which spans two-thirds of a pole pitch.
A17.4 v
B19.2 v
C12.2 v
D9.6 v
#78📘 EE Pocket Reviewer RojasEasy
What is the function of the damper windings in a large alternator?
AIt will reduce voltage fluctuations
BIt will reduce frequency fluctuations
CIt will increase stability
DNone of these
#79📘 EE Pocket Reviewer RojasEasy
The distribution of load between two alternators in parallel operation is changed using one of the following methods?
AChange the driving torque of the prime movers
BChange the frequency of the alternators
CChange the phase sequence of the alternators
DChange the excitation of the alternators
#80📘 EE Pocket Reviewer RojasEasy
The drop in the terminal voltage of an alternator due to armature reaction is countered by which of the following?