Determine the symmetrical components of the line current in line 'a' if one of the in phase impedance of its delta-connected load connected across lines 'ca' is removed. The delta load with impedance of \(10 \angle 0^\circ\) ohms per phase is supplied from a 220 volts, 60 cycle, 3-phase. Assume a phase sequence of a-b-c.
A star-connected balanced load takes 75 A from a balanced 3-phase, 4-wire supply. If the two supply lines of the fuses are removed determine the symmetrical components of the line currents after the fuses are removed.
A 20 MVA, 13.8 kV, 60 Hz, three-phase synchronous turbo alternator has a positive, negative and zero sequence reactances of 0.25, 0.35 and 0.15 respectively. If lines b and c are short-circuited, determine the subtransient fault current in line b. Assume the alternator is operating at no load and at rated voltage with the neutral of the alternator solidly grounded.
A2614 A
B2886 A
C2415 A
D2510 A
#4📘 1001 RojasHard
Two 3-phase transformers are connected in parallel at the primary as well as at the secondary sides. One is rated 10 MVA, 34.5/13.8 kV and 4% impedance while the other is rated 7.5 MVA, 34.5/13.8 kV and 5% impedance. The primary tapping point has a 3-phase short circuit MVA of 1000 MVA. Determine the fault current delivered to a 3-phase fault at the secondary side bus bars.
A13,501 A
B10,452 A
C12,532 A
D11,953 A
#5📜 EE Board October 1992📘 1001 RojasHard
A generator is rated 100 MVA, 15 kV, it is Y-connected, solid grounded and is operated at rated voltage at no-load and is disconnected from the rest of the system. Its positive and negative sequence reactances are each 0.10 p.u. and its zero sequence reactance is 0.05 p.u. Calculate in ohms of inductive reactance to be inserted in the neutral connection of the generator to limit the fault current for a single line to ground fault to the fault current of a symmetrical three-phase fault.
A0.0233 \(\Omega\)
B0.0225 \(\Omega\)
C0.0376 \(\Omega\)
D0.0325 \(\Omega\)
#6📘 1001 RojasHard
In a short circuit analysis, the positive, negative and zero sequence impedances are 0.20 pu, 0.20 pu and 0.25 pu, respectively, using a base MVA of 50. Estimate the fault current on the faulted lines if a double line to ground fault at the 138 kV level occurs.
A1204 A
B1011 A
C1090 A
D1104 A
#7📘 1001 RojasHard
A 15 MVA, 6,600 V, 60 Hz, Y-connected synchronous alternator has a positive, negative and zero sequence per unit reactance of 0.20, 0.20 and 0.10 respectively. The neutral of the generator is grounded through a reactor with a per unit reactance of 0.05 based on the generator rating. If a double line to ground fault occurs at the alternator terminals, estimate the current that flows in the reactor.
A5920 A
B5623 A
C6125 A
D6342 A
#8📘 1001 RojasHard
The secondary side of 5 MVA, 34.5/13.8 kV, 3-phase transformer is connected to a bus bar served by a 20 MVA, 13.8 kV, 3-phase alternator. The primary side of the transformer is tapped from an infinite bus. Estimate the fault current delivered to a 3-phase fault near the common bus bar. The transformer and alternator have 4% and 7.5% reactance, respectively.
A12,760 A
B18,900 A
C15,340 A
D16,400 A
#9📘 1001 RojasHard
Given the one line diagram as shown, determine the current delivered by generator A when a three-phase fault occurs at point P.
A172.5 A
B167.1 A
C145.5 A
D198.4 A
#10📘 1001 RojasHard
Given the one-line diagram as shown, determine the reactance of the limiting reactor x in order to limit the three-phase symmetrical fault power at point P to 400 MVA.
A0.65 \(\Omega\)
B0.40 \(\Omega\)
C0.52 \(\Omega\)
D0.46 \(\Omega\)
#11📜 EE Pre-Board August 2012📘 PowerhouseHard
A generator of 50 MVA, 4 kV, \(X_d'' = 25\%\) and a transformer of 50 MVA, 4.2 kV delta/115 kV wye grounded, operating on the 3.8 kV tap, where \(X_T = 10\%\), are to be connected into a single equivalent reactance. What is the single equivalent reactance on a 100 MVA, 110 kV base?
Aj0.6039 pu
Bj0.6667 pu
Cj0.8241 pu
Dj0.8663 pu
#12📜 EE Pre-Board March 2013📘 PowerhouseHard
In a 3-phase, 4-wire system, the current in line a has \(I_{a1} = 220\angle 0^\circ\) A and \(I_{a2} = 100\angle 60^\circ\) A. The current through the neutral conductor is \(300\angle -60^\circ\) A. Find the line current \(I_b\) in amperes.
A\(100\angle -300^\circ\)
B\(100\angle 120^\circ\)
C\(100\angle -60^\circ\)
D\(300\angle 240^\circ\)
#13📜 EE Pre-Board March 2013📘 PowerhouseHard
If the loads of a wye-connected transformer are \(I_a = 10\ \text{cis}\ (-30^\circ)\), \(I_b = 12\ \text{cis}\ 215^\circ\) and \(I_c = 15\ \text{cis}\ 82^\circ\), what is the phase b positive sequence component?
A\(13.4\ \text{cis}\ (-32.2^\circ)\)
B\(10.2\ \text{cis}\ 240^\circ\)
C\(12.27\ \text{cis}\ 208.4^\circ\)
D\(12.27\ \text{cis}\ (-31.6^\circ)\)
#14📜 EE Pre-Board August 2013📘 PowerhouseHard
In a 3-phase, 4-wire system, the current in line a has \(I_{a1} = 200\angle 0^\circ\) A and \(I_{a2} = 100\angle 60^\circ\) A. The current through the neutral conductor is \(300\angle -60^\circ\) A. Find the line current \(I_b\) in amperes.
A\(300\angle 120^\circ\)
B\(300\angle -60^\circ\)
C\(300\angle 240^\circ\)
D\(100\angle -30^\circ\)
#15📜 EE Pre-Board March 2014📘 PowerhouseHard
The sequence components of the line A current are as follows: \(I_{a0} = 14.13\angle 17.34^\circ\) A, \(I_{a1} = 708.26\angle -31^\circ\) A and \(I_{a2} = 2.98\angle 10.06^\circ\) A. Find the line current \(I_b\) in amperes.
A\(695\angle 205^\circ\) A
B\(695\angle -155^\circ\) A
C\(695\angle 151^\circ\) A
D\(695\angle 209^\circ\) A
#16📜 EE Pre-Board August 2014📘 PowerhouseHard
A synchronous generator having a subtransient reactance of 0.15 pu and operating at 5 percent above its rated voltage supplies a synchronous motor having a 0.2 pu subtransient reactance. The motor is connected to the generator by a transmission line and a transformer of total reactance 0.305 pu. A sudden three-phase short circuit occurs at the generator terminals. Determine the per unit subtransient fault current.
A−j6.443 pu
B−j7.443 pu
C−j9.079 pu
D−j10.079 pu
#17📜 EE Pre-Board March 2016📘 PowerhouseHard
A synchronous generator having a subtransient reactance of 0.15 pu and operating at 5 percent above its rated voltage supplies a synchronous motor having a 0.20 pu subtransient reactance. The motor is connected to the generator by a transmission line and a transformer of total reactance 0.305 pu. A sudden three-phase fault occurs at the generator terminals. Determine the per unit subtransient fault current.
A–j7.079 pu
B–j8.0789 pu
C–j9.079 pu
D–j10.079 pu
#18📜 EE Pre-Board March 2016📘 PowerhouseHard
The sequence components of the phase c current of a 3-phase system are as follows: \(I_{c0} = 0\), \(I_{c1} = 18.4\angle 88.4^\circ\), \(I_{c2} = 3.23\angle 48.2^\circ\). Find the phase b current in amperes.