Electrical Engineering · Question Bank

Philippine Electrical Code

7 of 33 questions match. Answer in your head first, then check the solution.

DifficultyAll 7Easy 7MediumHard
✕ Clear filters
#1📜 EE Pre-Board March 2013📘 PowerhouseEasy
A hermetic motor compressor has a full-load current of 25A. What is the allowable rating for branch disconnecting means?
A28.75 A
B30 A
C31.25 A.
D37.5 A
#2📜 EE Pre-Board August 2015📘 PowerhouseEasy
What is the minimum required ampacity of the feeder conductors supplying a 5A, single-phase motor and a 10A lighting load?
A14.25 A
B15.5 A
C17.5 A
D16.25 A
#3📜 EE Pre-Board March 2016📘 PowerhouseEasy
What is the branch circuit ampacity of a hermetic motor with a full load current of 16 A?
A15A
B20A
C25A
D30A
#4📜 EE Pre-Board March 2016📘 PowerhouseEasy
An office has a total of 500 square meters. Find the total lighting load for a unit of 28 volt-amperes per square meter.
A8KVA
B10KVA
C12KVA
D14KVA
#5📜 EE Pre-Board March 2017📘 PowerhouseEasy
How many 240 v, 20 A branch circuits are required to supply 60,000 va load?
A13
B14
C15
D12
#6📜 EE Pre-Board March 2018📘 PowerhouseEasy
The following are the given loads of a particular circuit: five 15 HP motors, three 5 HP motors, 8 kW lighting loads and 3.5 kW miscellaneous loads. Calculate the maximum demand in kW if the demand factor is 65%.
A78.64
B45.81
C51.12
D120.28
#7📜 EE Pre-Board August 2018📘 PowerhouseEasy
What is the maximum plug and cord rating of a 30 A branch circuit?
A24 A
B30 A
C26 A
D28 A