The secondary current of a 20 KV/7.79 KV autotransformer is 100 amperes. Determine the current that flows through the common winding.
A60 amps
B100 amps
C79 amps
D50 amps
#122📜 EE Pre-Board March 2015📘 PowerhouseEasy
In a T-T connected transformer, if the terminal voltage in the primary side is 220 volts, what is the voltage across the teaser transformer?
A127 volts
B190 volts
C220 volts
D110 volts
#123📜 EE Pre-Board August 2015📘 PowerhouseMedium
A 13.8 kV/480 V, 30-MVA three-phase transformer has a 0.03 pu resistance and 0.04 pu reactance. What is the transformer actual impedance referred to the primary?
A0.3174 Ω
B0.6348 Ω
C0.1587 Ω
D0.2749 Ω
#124📜 EE Pre-Board August 2015📘 PowerhouseMedium
A 20 kVA, 2000/220 V, single-phase transformer has a primary resistance of 2.1 Ω and a secondary resistance of 0.026 Ω. The corresponding leakage reactances are 2.5 Ω and 0.03 Ω. Determine the transformer per unit impedance.
A0.065 pu
B0.043 pu
C0.033 pu
D0.055 pu
#125📜 EE Pre-Board August 2015📘 PowerhouseEasy
A single-phase transformer is rated 110/440 V, 2.5 kVA. Leakage reactance measured from the low-tension side is 0.06 Ω. Determine the leakage reactance on the high-tension side in per unit.
A0.0124
B0.1984
C0.0496
D0.3963
#126📜 EE Pre-Board August 2015📘 PowerhouseEasy
Three units of 1:10 Transformers are connected in ∆/Y to supply a 3-phase load from a 400-v, 3-phase source. What is the line voltage on the load side?
A6,928 V
B3,464 V
C\(40\sqrt{3}\) V
D4,000 V
#127📜 EE Pre-Board August 2015📘 PowerhouseEasy
A 10:1 ideal transformer has a load of 0.1μF on the secondary. What is the load capacitance, as referred to the primary?
A1μF
B10μF
C0.01μF
D0.001μF
#128📜 EE Pre-Board August 2015📘 PowerhouseEasy
A 50-kVA single-phase transformer has on full-load a copper loss of 560 watts and iron loss of 500 watts. Calculate the efficiency at 25% of full-load for a power factor of 0.8 lagging.
A92.94%
B94.92%
C93.94%
D95.92%
#129📜 EE Pre-Board August 2015📘 PowerhouseMedium
The core loss of a 5-kVA single-phase transformer with normal voltage applied to the primary is 75 watts. The maximum efficiency occurs 60% of full- load kVA. What is the full-load efficiency of the transformer at 0.80 power factor?
A95.16%
B93.38%
C89.52%
D91.36%
#130📜 EE Pre-Board August 2015📘 PowerhouseEasy
A power transformer rated 50MVA, 34.5kV/13.8 kV is connected wye-wye. What is the rated primary line current?
A836.7 A
B1,449.3 A
C2,091.8 A
D1,207.7 A
#131📜 EE Pre-Board March 2016📘 PowerhouseMedium
A three phase wye delta connected, 50MVA, 345/ 34.5 Kv transformer is protected by differential protection. The current transformer on the high side for differential protection is 150:5. What is the current on the secondary side of CT’s?
A3.83A
B2.53A
C4.50A
D4.83A
#132📜 EE Pre-Board March 2016📘 PowerhouseEasy
What will happen to the current of a transformer when the temperature of the transformers winding increases?
Aremains unchanged
Bincreases
Cdecreases
Ddramatically unchanged
#133📜 EE Pre-Board March 2016📘 PowerhouseEasy
Transformers are used to change the value of the following EXCEPT
AAlternating current
BAlternating voltage
Cpower
Dresistance
#134📜 EE Pre-Board March 2016📘 PowerhouseEasy
When a V-V system is converted into Δ-Δ system, increase in the capacity of the system is _____ percent.
A86.8
B73.2
C66.6
D50
#135📜 EE Pre-Board March 2016📘 PowerhouseEasy
The applied voltage in a transformer is increased by 50 % and frequency is reduced by 50 %. The maximum core flux density will become ______________.
Asame
B1.5 times
C3 times
D5 times
#136📜 EE Pre-Board March 2016📘 PowerhouseEasy
A transformer has 4 % resistance and 6 % reactance drop. Find the voltage regulation at full-load 0.8 p.f. lagging.
A6.8 %
B5.8 %
C4.8 %
D160%
#137📜 EE Pre-Board March 2016📘 PowerhouseEasy
A 13.8 kV/440 V, 50 kVA single-phase transformer has a leakage reactance of 300 ohms referred to the 13.8 kV side. Determine the per unit value of the leakage reactance on the low voltage base.
A0.305
B0.4
C0.097
D0.079
#138📜 EE Pre-Board March 2017📘 PowerhouseEasy
Compute for the core loss if the transformer consumes 75 watts when it is connected across a 240 v source and taking 1.4 A. The primary resistance is 0.25 Ω
A73.6 W
B74.65 W
C74.75 W
D74.51 W
#139📜 EE Pre-Board March 2017📘 PowerhouseEasy
The primary of transformer has 200 turns and is excited by a 240 v, 60 Hz source. What is the maximum value of the core flux?
A4.04 mWb
B4.5 mWb
C4.13 mWb
D4.32 mWb
#140📜 EE Pre-Board March 2017📘 PowerhouseEasy
Which is not a characteristic of an ideal transformer?