Short Circuit Simulator
Draw the single-line diagram of a house — from the utility or a solo transformer down to the panels, breakers, motors and loads — and calculate the fault current at every bus by IEC 60909 or ANSI / IEEE Std 551. Single-phase, three-phase, or both.
How to use the simulator
- Place equipment. Pick a tool from the toolbar, then click on the canvas. Every system starts at a Utility source or a Generator. For a house tapping the utility's secondary line, either draw the utility transformer, or set the Utility source to a low-voltage single-phase system and enter the fault current available at the tap.
- Connect. Drag from one terminal dot to another. The Cable / Connector switch in the toolbar sets what new links are. Cables carry impedance from the PEC conductor table; connectors are zero-impedance jumpers.
- Single-phase taps. To take a single-phase branch off a three-phase or 120/240 V bus, select the link and set its Phase tap: A-N for 230 V from a 400/230 V system, or A-B for 230 V line-to-line from a 115/230 V centre-tapped secondary.
- Breakers and switches sit between a bus or panel and the outgoing cable. Enter each breaker's interrupting rating; the simulator checks it against the fault current at its line side.
- Choose the method in Study settings (click an empty part of the canvas), then press Run short circuit.
Method notes. Each phase and neutral conductor is modelled separately, so single-phase, three-phase and mixed systems are solved directly. IEC 60909-0 uses the equivalent voltage source c·Un at the fault, KT and KG impedance corrections, motor R/X = 0.42 (LV), and the κ peak factor (method B when more than one source contributes). ANSI / IEEE Std 551 (first-cycle, C37.13 low voltage) uses the prefault voltage, motor reactance multipliers (1.67 below 50 hp, 1.2 for 50–1000 hp), and breaker multiplying factors from the test X/R ratios in Table 10-1. Centre-tapped transformers use the half-winding model (ZH = 0.5R + j0.8X, ZX = R + j0.4X), which gives the 1.5R / 1.2X line-to-neutral factors in the Bussmann handbook. Conductor data: PEC 2017 Table 10.1.1.9.
Getting started
Load a template from the Template list, or press New and start with a Utility source or a Generator. Pick an element from the toolbar and click on the canvas to place it. Every diagram needs at least one source.
Connecting
Drag from one terminal dot to another, or choose the Cable or Connector tool and click the two elements you want to join. The wire tool stays on until you press Esc. Cables use impedances from the PEC conductor table; connectors are zero-impedance jumpers.
A breaker or switch has a line terminal at the top and a load terminal at the bottom. Put it between the bus or panel and the outgoing cable.
Single-phase branches
Select the link that starts the branch and set its phase tap: A-N for 230 V from a 400/230 V system, A-B for a 230 V line-to-line service from a 230/115 V centre-tapped secondary. Leave every other link at its default.
Editing and tidying
Click any element or link to edit it in the panel on the right. Drag a segment of a selected link to re-route it, and drag the round handle at either end to reconnect it to another terminal. Delete removes the selection, Ctrl+Z and Ctrl+Y undo and redo, Ctrl+D duplicates and Esc cancels. Drag empty canvas to pan and use the mouse wheel to zoom.
Running the study
Click an empty part of the canvas to choose IEC 60909 or ANSI / IEEE 551 and the other study settings, then press Run short circuit. Fault currents are tagged on every bus, panel and breaker; hover a tag to see each fault type. Ratings that are exceeded show in red. The results tables, the PDF report and the step-by-step working are below the editor.
Saving
Members can save diagrams to their account. Anyone can export and import JSON, download a PNG, or print the report to PDF.
Calculation method
IEC 60909-0; IEEE Std 551-2006
IEC 60909 gives the initial symmetrical current \(I''_k\) from an equivalent voltage source \(c\,U_n\) at the fault, with correction factors on transformers and generators. Use it for IEC-rated equipment (breakers rated by \(I_{cu}\)).
ANSI / IEEE 551 gives the first-cycle symmetrical current at the prefault voltage, with motor reactance multipliers and breaker multiplying factors based on the test X/R. Use it for UL 489 / ANSI-rated breakers, which is most moulded-case breakers sold in the Philippines.
Voltage factor c (low voltage)
IEC 60909-0, Table 1
The factor that raises the source voltage to cover operation above nominal. For maximum fault currents in low-voltage systems, use 1.05 when the voltage tolerance is +6% and 1.10 when it is +10%. Above 1 kV the simulator always uses 1.10.
Prefault voltage
IEEE Std 551-2006, Ch. 4
The voltage at the fault point just before the fault, in per unit of the nominal voltage. ANSI practice is 1.00 pu unless the system is known to run higher.
Conductor temperature
PEC 2017 Part 1, Table 10.1.1.9 notes; IEC 60909-0, 4.3.1
Cable resistance is corrected from the PEC table temperature of 75 °C with \(R_T = R_{75}[1 + \alpha (T - 75)]\). Lower temperature means lower resistance and higher fault current.
Use 20 °C for maximum fault currents (the IEC condition), or 75 °C to match a hand calculation that uses the PEC table values directly.
Motor contribution
IEC 60909-0, 3.8; IEEE Std 551-2006, Ch. 9
Running induction motors feed current into a fault for the first few cycles. Untick to see the fault current from the supply alone. In a typical house the contribution is a few tens of amperes; it matters with large pumps or many compressors on a three-phase supply.
Source system
The conductors the source provides. Choose 3φ 4-wire for a normal utility primary (grounded wye). For a house that taps the utility's 230/115 V secondary line and you know the fault current at the tap, choose 1φ 3-wire and enter that fault current; otherwise draw the utility transformer and secondary line.
Source voltage
Nominal line-to-line voltage of the source (line-to-neutral for a 1φ 2-wire L-N source). Examples: 13.8, 34.5 or 69 kV for a utility primary, 0.23 kV for a 230/115 V secondary tap.
Infinite bus
Treats the source impedance as zero. Use it when the utility fault level is unknown; the results are then the highest possible and conservative for equipment ratings. For a large utility supplying a small transformer the difference is usually small.
Available fault current
IEC 60909-0, 6.2
The fault current the utility can deliver at this point, from the utility's system study. The source impedance is \(Z_Q = c\,U_n / (\sqrt{3}\,I''_{kQ})\) for three-phase sources, or \(c\,V / I\) for single-phase ones (c = 1 for ANSI).
Ask the utility for the three-phase and line-to-ground values at the primary, or the line-to-line value at a secondary tap.
Source X/R
IEEE Std 551-2006, Ch. 4
Reactance-to-resistance ratio of the source impedance. It splits \(|Z_Q|\) into R and X and sets the peak current. Distribution feeders are typically 5 to 15; use the utility's value when you have it.
Ground-fault current
IEC 60909-0, 6.2; Anderson, Analysis of Faulted Power Systems
The line-to-ground fault current at the source, used to find the zero-sequence impedance \(Z_{Q0} = \sqrt{3}\,c\,U_n / I''_{k1Q} - 2 Z_{Q1}\). Leave 0 to take \(Z_0 = Z_1\). For a 1φ 3-wire tap this field is the line-to-neutral fault current instead; 0 takes it equal to the line-to-line current.
Ground-fault X/R
X/R of the ground-fault loop \(2Z_1 + Z_0\). Leave blank to use the same X/R as the three-phase source impedance.
Generator status
Out of service removes the generator from the calculation. To model a transfer switch, give the generator and the utility their own switches and change which one is closed.
Generator system
The conductors the generator provides: 3φ 4-wire for a three-phase genset with neutral, or a single-phase arrangement for a portable unit.
Rated voltage
IEC 60909-0, 6.6
Rated line-to-line voltage of the generator. Under IEC, if it differs from the system voltage, the correction factor \(K_G\) includes the ratio \(U_n/U_{rG}\).
Subtransient reactance x″d
IEEE Std 551-2006, Ch. 6
Sets the generator's contribution in the first cycles: \(Z_G = x''_d\,U_{rG}^2 / S_{rG}\). Small diesel gensets are typically 12–20%; use the manufacturer's value when you have it.
Zero-sequence reactance x₀
Used only for ground faults with a solidly grounded neutral. Typically about half of \(x''_d\) or less.
Generator X/R
Reactance-to-resistance ratio of the generator. Small gensets are typically 5 to 15.
Rated power factor
IEC 60909-0, 6.6.1
Used only by IEC, in \(K_G = (U_n/U_{rG})\,c_{max} / (1 + x''_d \sin\varphi_{rG})\). Gensets are usually rated at 0.8.
Generator neutral
Solidly grounded gives a zero-sequence path, so the generator feeds ground faults. Ungrounded removes it.
Transformer type and connection
Kersting, Distribution System Modeling and Analysis
Single-phase centre-tapped units give a 3-wire secondary (e.g. 230/115 V). Single-phase 2-wire units give one secondary voltage. For three-phase units the connection decides the ground-fault path: a delta primary blocks the utility's zero-sequence impedance, a grounded-wye secondary (Dyn, YNyn) supplies a neutral.
Primary connection
The two conductors of the supply the primary winding is connected across. Line-to-line (A-B) is common for 34.5 kV units; line-to-neutral (A-N) for units on 13.8 kV grounded-wye laterals. Enter the matching winding voltage in Rated primary.
Transformer rating
Nameplate kVA. With %Z it sets the transformer impedance \(Z_T = (\%Z/100)\,V^2/S\).
Rated primary voltage
Voltage across the primary winding: 7.97 kV for a unit connected line-to-neutral on 13.8 kV, 34.5 kV for one connected line-to-line on 34.5 kV. The simulator warns when this differs from the supply by more than 10%, because the secondary voltage would be off by the same ratio.
Rated secondary voltage
Line-to-line secondary voltage; for a centre-tapped unit, the full winding (0.23 kV for 230/115 V, 0.24 kV for 240/120 V).
Impedance %Z
Transformer nameplate or test report
The percent impedance on the nameplate. It is the main limit on fault current at the secondary: \(I_{FL} \times 100 / \%Z\) with an infinite source. Small pole-mounted units are typically 1.5–3%.
Transformer X/R
Cooper Bussmann, Short Circuit Current Calculations
Splits the impedance into \(R_T = Z_T/\sqrt{1 + (X/R)^2}\) and \(X_T = R_T\,(X/R)\). Small single-phase units are typically 1–2. X/R also changes the ratio between the 115 V and 230 V faults of a centre-tapped unit, from 1.33 (X/R = 0) towards 1.67. Use 0 only to reproduce a hand calculation that neglects reactance.
Secondary conductors
For a 2-wire unit: two line conductors (ungrounded, e.g. 230 V L-L), or a line and a grounded neutral (e.g. 230 V L-N).
Secondary neutral
Solidly grounded is normal practice and gives the neutral and ground-fault path. Ungrounded removes it.
Breaker status
An open breaker disconnects everything downstream; those buses are shown as de-energized.
Frame and trip rating
Frame size (AF) and trip rating (AT), shown on the drawing and in the report. They do not enter the fault calculation.
Interrupting rating
IEEE Std 551-2006, Table 10-1; IEC 60947-2
The breaker's short-circuit interrupting rating from its label. Under ANSI the fault current is first multiplied by the factor for the circuit's X/R and then compared with this value. Under IEC it is the ultimate breaking capacity \(I_{cu}\), compared with \(I''_k\).
Breaker type (ANSI)
IEEE Std 551-2006, Table 10-1
Sets the test X/R used for the multiplying factor: moulded-case and insulated-case breakers 1.73 (up to 10 kA), 3.18 (10–20 kA) or 4.9 (above 20 kA); LV power breakers 6.59 unfused, 4.9 fused.
Making capacity Icm (IEC)
IEC 60947-2, Table 2
Compared with the peak current \(i_p\). Leave blank to use the minimum \(I_{cm} = n\,I_{cu}\): n = 1.5 up to 6 kA, 1.7 up to 10 kA, 2.0 up to 20 kA, 2.1 up to 50 kA, 2.2 above. These n values were entered from IEC 60947-2 as known to the author; check them against your copy, or enter the manufacturer's \(I_{cm}\).
Switch status
Closed switches have zero impedance; an open switch disconnects the downstream side. Use two switches to model a transfer switch between utility and generator.
Short-circuit rating
IEEE Std 551-2006, Table 10-1
The bus or panel short-circuit (bracing) rating. Leave 0 for no check. Under ANSI the duty uses the test X/R of 4.9 listed for low-voltage busway.
Motor rating
IEEE Std 551-2006, Table 9-1
Output rating in hp or kW. The apparent input is \(S = P / (\eta \cos\varphi)\). Under ANSI the rating also selects the first-cycle multiplier: 1.67 below 50 hp, 1.2 from 50 to 1000 hp, 1.0 above.
Quantity
Number of identical motors connected at this point. Their impedances are combined in parallel.
Connection
Auto uses all phases on a three-phase bus, line-to-line on a 230 V L-L or 230/115 V bus, and line-to-neutral on an L-N bus. Choose a phase pair to place a single-phase motor on a three-phase bus.
Efficiency and power factor
Used to convert the output rating to the input kVA, \(S = P / (\eta \cos\varphi)\). 0.85 for both is typical of small motors.
Locked-rotor current
IEC 60909-0, 6.8; IEEE Std 551-2006, Ch. 9
Starting current as a multiple of full-load current. It sets the subtransient impedance \(Z_M = (1/\mathrm{LRC})\,U^2/S\). Typically 5–7 for induction motors.
Motor X/R
IEC 60909-0, 6.8
Leave blank for 2.38, which is the IEC value R/X = 0.42 for low-voltage motors including their connecting cables.
Lumped load
Total load at this point in kVA. Only the motor portion contributes to fault current; lighting, heating and electronics do not.
Motor portion
IEEE Std 551-2006, Ch. 9
Percentage of the load that is induction motors (aircon compressors, pumps, fans). That part is modelled like a motor with the locked-rotor current below.
Cable or connector
A cable carries impedance from the PEC table. A connector is a zero-impedance jumper, for example between the source and the transformer primary, or between a breaker and the panel it is mounted in.
Phase tap
Leave as "same" for ordinary links. Set it on the link that starts a branch with fewer conductors: A-N for 230 V from a 400/230 V system, A-B for 230 V line-to-line from a 230/115 V centre-tapped secondary, A-B-N for a two-phase three-wire branch.
Route on the drawing
Changes only how the link is drawn. You can also drag a segment on the canvas; choosing a style here resets the offsets.
Cable length and parallel sets
Route length in metres. Parallel sets divide the impedance: \(Z_c = (R + jX)\,L / (1000\,n)\).
Conductor material and installation
PEC 2017 Part 1, Table 10.1.1.9
Selects the PEC table column: copper or aluminium, in PVC, aluminium or steel conduit. Steel conduit has higher reactance. Overhead uses the PVC-conduit reactance, a reasonable value for triplex and duplex service drops. Custom lets you enter R and X per km from the manufacturer.
Conductor size
PEC 2017 Part 1, Table 10.1.1.9
Phase conductor size in mm². The neutral can be a different size. The table values are ohms to neutral per 305 m at 75 °C; the panel below shows the values used at the study temperature.
Custom R and X
Per-conductor resistance and reactance in Ω/km at the study temperature, from the cable manufacturer. The neutral R defaults to the phase value.
Study
- Bolted (zero-impedance) faults. Each phase and neutral conductor is modelled separately, so single-phase, three-phase and mixed systems are solved directly.
- Faults are calculated at every bus, panel and breaker (line side). Fault types: 3φ, L-L, L-L-N and L-N on 4-wire systems; 3φ, L-L and L-G on 3-wire systems; L-L and L-N on 1φ 3-wire; one type on 2-wire branches.
- Static (non-motor) load is ignored, as both standards require. Ground faults on 4-wire systems return through the neutral conductor; the protective-earth conductor is not modelled.
- Conductor temperature default 20 °C (maximum fault current). The PEC table values are at 75 °C and are corrected with α = 0.00323 (Cu) / 0.00330 (Al).
IEC 60909-0
- Equivalent voltage source c·Un at the fault. cmax = 1.05 (LV, +6% tolerance) or 1.10 (LV +10%); 1.10 above 1 kV. The utility impedance also uses c.
- Transformer correction KT = 0.95·cmax ÷ (1 + 0.6·xT); generator correction KG = (Un/UrG)·cmax ÷ (1 + x″d·sin φ).
- Peak ip = κ√2·I″k, κ = 1.02 + 0.98e−3R/X; method B (1.15κ, max 1.8 LV) when more than one source contributes. Unbalanced faults use the 3φ κ. Breaking current Ib is shown as I″k (far-from-generator, conservative).
- Breaker check: I″k ≤ Icu and ip ≤ Icm, with Icm = n·Icu (n = 1.5 up to 6 kA, 1.7 up to 10 kA, 2.0 up to 20 kA, 2.1 up to 50 kA, 2.2 above, per IEC 60947-2) unless entered.
ANSI / IEEE Std 551 (first cycle, C37.13 LV)
- Prefault voltage 1.00 pu (editable). X/R from the complex network impedance.
- Ipeak = √2(1 + e−2πτ/(X/R))·Isym, τ = 0.49 − 0.1e−(X/R)/3; Iasym (½ cycle) = Isym√(1 + 2e−2π/(X/R)).
- Breaker duty multiplied by MF = Ipeak(X/R) ÷ Ipeak(test X/R) when above 1. Test X/R (Table 10-1): molded/insulated case 1.73 (≤ 10 kA), 3.18 (10–20 kA), 4.9 (> 20 kA); LV power breaker 6.59, fused 4.9; bus/panel 4.9.
Element defaults
- Utility: fault current and X/R as entered; Z₀ = Z₁ if no ground-fault current is given; for a 1φ 3-wire tap, L-N current = L-L current unless entered. "Infinite bus" makes the source impedance negligible.
- Transformer: %Z and X/R from the nameplate. A centre-tapped secondary uses the half-winding model ZH = 0.5R + j0.8X, ZX = R + j0.4X, which gives the Bussmann 1.5R / 1.2X L-N factors. Secondary neutral solidly grounded by default. Rated voltages must match the supply across the winding (e.g. 7.97 kV line-to-neutral on 13.8 kV).
- Cables: PEC 2017 Table 10.1.1.9 (600 V, three single conductors in conduit, 60 Hz). "Overhead" uses the PVC-conduit reactance. Each conductor is R + jX without mutual coupling; the neutral can be a different size; parallel sets divide the impedance. New cables default to 10 m, 8.0 mm² Cu in PVC.
- Motors: Z = (1/LRC)·U²/S with S = P ÷ (η·pf); LRC 6, η and pf 0.85, X/R 2.38 (IEC R/X 0.42 for LV). ANSI first-cycle multipliers 1.67 (< 50 hp), 1.2 (50–1000 hp), 1.0 (larger).
- Lumped load: only the motor portion contributes (default 30%, LRC 5).
- Generator: x″d 15%, x₀ 6%, X/R 8, pf 0.8, neutral solidly grounded; Z₂ = Z₁.
- Breakers and switches: zero impedance when closed; open ones disconnect the downstream side.
Results
Fault currents by location
Equipment duty
Step-by-step computation
For preliminary design and checking only. Results are bolted-fault values based on the data you enter and typical conductor data from the PEC. Verify against utility-supplied fault levels, transformer test reports and manufacturer data before choosing equipment ratings. References: IEC 60909-0; IEEE Std 551-2006 (Violet Book); Cooper Bussmann, Short Circuit Current Calculations; Philippine Electrical Code Part 1 (2017) Table 10.1.1.9.